9.10.3
Con
fi
guration of analog inputs
“
E1
”
and
“
E2
”
9.10.3.1
Signal adaption E1 and E2
If required, an adaptation of the speci
fi
cation signal / speed characteristic curve is possible.
Information
Setting options depending on the version of the software available!
These settings are mostly practical for the operating mode with rotational speed speci
fi
cation over an
external signal. In operating modes (as of 2.01) this setting is not suited for in
fl
uencing the regulation
process.
IO Setup
0
E1 Modus
E1 Modus
|
0
|
= E1 min. / E1 max. without function (factory setting)
|
1
|
= Offset / turn
|
2
|
= signal range
|
3
|
= Hysteresis setting On / Off (function depending on the version of the software
available)
IO Setup
0 %
E1 Min.
E1 Min.
Setting range: 0 - 100 %
Factory setting: 0 %
IO Setup
0 %
E1 max.
E1 max.
Setting range: 0 - 100 %
Factory setting: 100 %
IO Setup
0
E2 Mode
E2 Mode
|
0
|
= E2 min. / E2 max. without function (factory setting)
|
1
|
= Offset / turn
|
2
|
= signal range
IO Setup
0 %
E2 min.
E2 min.
Setting range: 0 - 100 %
Factory setting: 0 %
IO Setup
0 %
E2 max.
E2 max.
Setting range: 0 - 100 %
Factory setting: 100 %
Operating Instructions
Fcontrol
–
model series FXDM25/32AM
Programming
L-BAL-E212-GB 1451 Index 003
Part.-No.
78/123