background image

Icontrol Basic

FSDM2.6...62

Frequency inverter for 3 ~ fans

Speed controller with 0...10 V input for presetting the fan speed

Operating Instructions

Keep for reference!

Software version:  D2732A from Version 1.03

L-BAL-E160-GB 1701 Index 004

Part.-No. 

english

CZ

|

D

|

E

|

F

|

GB

|

I

|

PL

|

RU

|

S

|

 

 www.ziehl

­

abegg.com

Summary of Contents for iControl FSDM2.6

Page 1: ...for 3 fans Speed controller with 0 10 V input for presetting the fan speed Operating Instructions Keep for reference Software version D2732A from Version 1 03 L BAL E160 GB 1701 Index 004 Part No engl...

Page 2: ...4 6 Temperature in uences during commissioning 11 5 Electrical installation 11 5 1 Safety precautions 11 5 2 EMC compatible installation 11 5 2 1 Interference emission and installation of cables 11 5...

Page 3: ...es 18 6 Start up 18 6 1 Prerequisites for commissioning 18 7 Diagnostics Faults 19 8 Enclosure 22 8 1 Technical data 22 8 1 1 Maximum loading dependent on switching frequency line voltage and ambient...

Page 4: ...ce of unauthorized repairs or modi cations 1 4 Copyright These operating instructions contain copyright protected information The operating instructions may be neither completely nor partially photoco...

Page 5: ...ions and skills for these jobs In addition they must be knowledgeable about the safety regulations EU EC directives rules for the prevention of accidents and the corresponding national as well as regi...

Page 6: ...urer in writing Use only genuine spare parts genuine wearing parts genuine accessories from ZIEHL ABEGG Th ese parts were speci cally designed for the device There is no guarantee that parts from non...

Page 7: ...0 mA PWM 3 3 Maintenance The device must be checked for soiling and if necessary cleaned in periodic intervals 3 4 Transport The device is packed ex factory to suit the transport method previously agr...

Page 8: ...cooling air feed as well as unobstructed outgoing air discharge minimum space requirement The device should be installed in a location where it will not be disturbed but at the same time can be easil...

Page 9: ...29 01 2016 1 3 2 Drill fastening point 1 Screw in at head screw up to a distance of approx 2 mm and mount the device Remove the terminal compartment cover Align the device and mark the position of bo...

Page 10: ...points GM00002B_M 28 01 2016 1 2 3 4 5 6 8 7 Drill 8 fastening points Screw in fastening point screws 1 4 up to a distance of approx 5 mm and mount the device Tighten fastening point screws 1 4 Screw...

Page 11: ...and all electrical supply facilities locked Access is only allowed for authorized persons using a key or special tool Operating the device with the housing cover removed is prohibited because energize...

Page 12: ...m EN 61000 3 12 valid for equipments with rated current 16 A and 75 A connected to public low voltage systems This equipment complies with IEC 61000 3 12 provided that the short circuit power SSC is g...

Page 13: ...connection The motor leads are connected to the terminals PE U V W Comply with the motor data rating plate regarding the type of connection Y or D U f characteristic curve and technical data Informat...

Page 14: ...ugged at top factory setting A maximum of six individual thermistors DIN 44081 or DIN 44082 may be connected in series to a single device J1 TP Motor with thermostats TB For motor with thermostats TB...

Page 15: ...ng 0 10 V factory setting Control via external setting signal 0 10 V or Speed setting by external potenziometer 10 k at terminals 10 V and GND pick of off at terminal E1 E1 D1 GND 0 10 V Analog In 1 E...

Page 16: ...ical data und connection diagram It is not permissible to connect voltage outputs of several devices to each other It is not permissible to connect voltage outputs in the device to each other 5 9 Volt...

Page 17: ...troller shunt with mains voltage Mutual locking of mains contactor and bypass protection Time delay of at least 1 second during switching When the contactor is switched off at the inverter output the...

Page 18: ...rs can be addressed automatically by an additional connection The device can be communicated with using the hand held terminal type A G 247NW Connection by cable via the MODBUS interface or wirelessly...

Page 19: ...this op eration permissible for the controller in case of reduced operation due to too high an internal temperature no fault message is sent via the relay With a drop in temperature the modula tion ri...

Page 20: ...ing off of error message when the volt age exceeds the xed limit for at least 5 s Check line voltage 13 de energized 13 14 interrupted Line voltage too high Line voltage above xed limit for longer th...

Page 21: ...s After every detection IGTB Recovery Flag is set there is a 30 s wait until a new attempt is started The respective errors must alway have a shorter interval than 5 minutes started after restart The...

Page 22: ...rating plate rated voltage rated temperature cos 0 8 at the output 2 At rated voltage cos 0 8 at the output values for different speci cations on request 3 Example for power of a 4 pole motor For the...

Page 23: ...ns Interference immunity EN 61000 6 2 industrial applications Harmonics current For devices 16A according to EN 61000 3 2 see Electrical Installation Harmonics current for devices 16A For devices 16 A...

Page 24: ...50 C 55 C 40 C 50 C 55 C F S DM32A Q 32 0 A 32 0 A 28 0 A 32 0 A 30 0 A 26 0 A F S DM39A Q 39 0 A 39 0 A 39 0 A 39 0 A 39 0 A 37 0 A F S DM46A Q 46 0 A 46 0 A 42 0 A 46 0 A 43 0 A 39 0 A F S DM62A Q...

Page 25: ...52 7 A 46 7 A 42 5 A 52 7 A 46 7 A 40 8 A Maximum motor current for 16 kHz depending on line voltage and ambient temperature Type 208 V 15 415 V 6 over 415 V 6 480 V 10 40 C 50 C 55 C 40 C 50 C 55 C...

Page 26: ...bei Q in Typ Main switch only at Q in type 9 1 J1 E1 1 E1 2 TB TP 0 20 mA 0 10 V 10 V PWM 15 28 V PWM 5 6 Temperaturf hler Thermistors TP Thermostatschalter Thermostats TB UMUN11K2 14 01 2016 2 Nicht...

Page 27: ...FSDM5 FSDM17 FSDM25 FSDM32 FSDM62 Operating Instructions Icontrol Basic model series FSDM2 6 62 Enclosure L BAL E160 GB 1701 Index 004 Part No 27 28...

Page 28: ...nical support for control systems ventilation technology phone 49 0 7940 16 800 Email fan controls service ziehl abegg de Our worldwide contacts are available in our subsidiaries for deliveries outsid...

Reviews: