Code
Relay
K1
Explanation
Reaction of device
Adjustment
17
de-energized, 13 -
14 interrupted
Overload fault
The controller was switched off by the
current limitation.
The error is set after detecting 4 times
(I
2
t-process; maximum overload applied
for 60 s).
After every detection (IGTB Recovery
Flag is set) there is a 30 s wait until a
new attempt is started.
The respective errors must alway have a
shorter interval than 5 minutes (started
after restart). The modulation is switched
off immediately after every detection.
Check load of the device.
Reset by enable or line voltage ON/OFF.
Operating Instructions
Icontrol Basic
–
model series FSDM2.6...62
Diagnostics / Faults
L-BAL-E160-GB 1701 Index 004
Part.-No.
21/28