3.4
Transport, storage
Attention!
•
Observe the weight speci
fi
cations (see rating plate) and the permissible carrying loads of the means
of transport.
•
Wear safety clothing / shoes and cut-resistant safety gloves when handling.
•
Do not transport the fan by the connecting cable!
•
Avoid shocks and impacts to the device during the transport.
•
Avoid extreme humidity, heat or exposure to cold (see technical data).
•
Watch out for possible damage to the packaging or fan.
•
Fix pallets during transport.
•
Do not stack pallets.
•
Only handle with suitable hoisting gear.
•
Position the lifting beam transversely to the motor axis. Pay attention to adequate width of the lifting
beam.
•
Never stand underneath the suspended fan because defective transport equipment could cause
death.
•
Store the fan / motor in the original packaging in a dry area protected from the weather and protect
it from dirt and weather until
fi
nal installation.
•
Avoid prolonged storage; we recommend a maximum of one year (consult the manufacturer before
starting if stored for longer).
•
Inspect the bearing for proper operation prior to installation.
–
Recommendation: Turn the impeller evenly by hand to avoid jamming and damaging the
bearing.
•
Transport the fan(s) either in the original packaging or, in the case of larger fans, on the dedicated
transportation
fi
xtures.
–
axial fans: holes drilled in support arms, wall ring plates and motor block
–
centrifugal fans depending on type: holes drilled in the housing
fl
ange, motor block, fastening
brackets and support plates,
•
Radial impellers, fans with scroll RG.., RD.. or built-in fans type ER../GR.., WR.. are generally
delivered on europallets, and can be transported using lift trucks.
•
Design RG.. / RD.. / ER.. / GR../ WR../HR..
: Fan unit may only be lifted and transported when
using a suitable hoisting device (load spreader). Ensure suf
fi
cient cable or chain length.
•
Design FV.. / DN..
: The fan must be fastened to 4 points during transport so the
fl
anges do not
warp.
•
Design WR: maximum permissible number for lifting fan units mounted on top of one another
Size
External dimensions [mm]
Permissible number
1
607 x 607
5
2
760 x 760
4
3
912 x 912
3
Attention!
Lifting several fan units next to one another is prohibited!
3.5
Disposal / recycling
Disposal must be carried out professionally and in an environmentally friendly way in accordance with
the respective national legal stipulations.
"
Separate the materials by type and in an environmentally friendly way.
"
If necessary, commission a specialist company with the waste disposal.
Assembly instructions
PMblue
Product overview
L-BAL-F073-GB 2033 Index 003
Part.-No. 00703805-GB