background image

4.2 Mains connection

The mains connection is made for 1 ~  types at the terminals: PE, L1, N, for 3 ~ types at 
the terminals PE, N, L1, L2, L3 (see connection diagram depending on type). Here, it 
must be strictly observed that the mains voltage lies within the allowable tolerance 
speci

cations (see Technical data and nameplate af

xed to the side).

The mains voltage must comply with the EN 50160 quality characteristics and the 
de

ned standard voltages in IEC 60038!

4.3 Motor connection

The motor connection is made depending on type (see connection diagram). Several 
motors can be connected to the device - the maximum total current of all motors must 
not exceed the current rating for the device.
Motor protection via connection of TB thermostatic switches (not suitable for PTC 
thermistors). When the thermostatic switches are triggered (motor fault), the device 
switches off. Restart is performed once the drive has cooled down either by switching 
the mains voltage off and on again (after approx. 2 minutes) or via the switch.

Attention!

If multiple motors are connected, connect thermostatic switches to the TK - TK terminals 
in series.

Special function: Automatic restart when motor has cooled down

Automatic restart when motor has cooled down if the both terminals 

J

-

J

are bridged. This special 

function is admissible only after consultation with the motor manufacturer and the system operator 
must be informed about this.

4.4 Operating indicator contacts for type S-..KT

Operating indicator contacts, e.g. for shutter control (for contact load, see connection 
diagram).

Potential-free contacts

If the device is switched on when mains voltage is applied (step 1 or higher), the 
internal relay is energised (=> terminals 11 - 14 bridged).

In the case of switch-off via the remote control (RT - RT terminals interrupted) and 
in the case of motor fault (TK - TK terminals interrupted), the relay is de-energised 
(=> terminals 11 - 12 bridged).

 Contacts to which mains voltage is applied

The L

 and N

 terminals are directly connected to the mains connection, meaning 

that there is continuous voltage when mains voltage is applied, even in the switch 
position 

0

.

The mains voltage at terminal L' is switched via the internal relay (voltage ON 

  L' 

- L

 terminals bridged).

Operating Instructions 

S-ET... / S-DT...

Installation

L-BAL-E058-GB 1931 Index 002

Part.-No. 

7/12

Summary of Contents for S-ET Series

Page 1: ...S ET S DT Switching units for 1 and 3 motors Operating Instructions Keep for reference L BAL E058 GB 1931 Index 002 Part No english D GB F NL PL www ziehl abegg com...

Page 2: ...3 1 Function 5 3 2 Maintenance 5 3 3 Transport 5 3 4 Storage 5 3 5 Disposal recycling 6 4 Installation 6 4 1 General notes 6 4 2 Mains connection 7 4 3 Motor connection 7 4 4 Operating indicator conta...

Page 3: ...ure developments construction methods and technical data given are subject to alteration We do not accept any liability for possible errors or omissions in the information contained in data illustrati...

Page 4: ...ing of the motor fan the appropriate instructions in the drive documentation must be observed Attention Even after switching off dangerous temperatures can still occur in and on the device Attention A...

Page 5: ...OFF or speed change over of one or more motors via the integrated switch The maximum total current of all motors should not exceed the rated current of the device Integrated operating indicator lamp...

Page 6: ...e the appropriate mounting devices for proper installation of the unit Do not mount equipment on vibrating base Do not allow drilling chips screws and other foreign bodies to reach the device interior...

Page 7: ...cted connect thermostatic switches to the TK TK terminals in series Special function Automatic restart when motor has cooled down Automatic restart when motor has cooled down if the both terminals J J...

Page 8: ...age at terminal 12 if fan is not running also in switch position 0 18 04 2008 v_kla_steu_1dra_feder_2dra VSD M AC 230 V M 1K M AC 230 V M 2K M AC 24 V 230 V M 3K L L N L L N 11 14 N 12 5 Enclosure 5 1...

Page 9: ...le ambient temperature 40 C Housing plastic housing ABS Housing protection IP54 Weight approx 1 1 kg 5 2 Connection diagram S ET1KT N L1 PE Netz Line 1 230 V 50 60 Hz 12 11 14 N L L RT RT TK TK 1 5 0...

Page 10: ...tern with internal thermostats 2 TB L2 L3 S DT2S K T N L1 PE Netz Line 3 400 V 50 60 Hz 12 11 14 N L L RT RT TK TK 1 5 0 1 Aus Ein Off On 3 1 Wenn Funktion nicht ben tigt wird Klemmen br cken If funct...

Page 11: ...DT32KT N L1 PE Netz Line 3 400 V 50 60 Hz 12 11 14 N L L RT RT TK TK 1 5 0 1 Aus Ein Off On 3 1 Wenn Funktion nicht ben tigt wird Klemmen br cken If function is not needed terminals must be bridged 1...

Page 12: ...49 0 7940 16 504 info ziehl abegg de http www ziehl abegg de 5 5 Service information If you have any technical questions while commissioning or regarding malfunctions please contact our technical supp...

Reviews: