Figure 5-3-5-01
(1) Frequency inverter
(2) Motor temperature monitoring
5.3.6
Temperature monitoring
The elevator machine is supplied with an EMC cable (1) gland.
Motor cable with EMC-optimised screening
Motor cable with pigtail
Figure 5-3-6-01
The motor cable must be positioned so that the metal
strip (2) is in contact with the screening (3) of the motor
cable.
Figure 5-3-6-02
(1) EMC-cable gland
(2) Metal strip
(3) Screening of the motor cable
Figure 5-3-6-03
The motor cable is designed with a pigtail (2).
Connect the pigtail (2) to the brass screw (3) for the
protective conductor.
Figure 5-3-6-04
(1) EMC-cable gland
(2) Pigtail
(3) Brass screw for protective conductor
5.3.7
Temperature monitoring
•
The temperature monitoring by the PTC thermistor or temperature sensor (PT100) must be
evaluated.
•
Only connect to the inputs suitable for the relevant monitoring type.
•
Maximum permissible test voltage for PTC thermistors: 2.5 VDC.
•
When monitoring with a temperature sensor (PT100), the monitoring unit must be set to the limit
value (
°
C) speci
fi
ed in the connection diagram.
Translation of the original operating instructions
ZAtop SM250.45B
Electrical installation
A-TBA17_04-GB 2023/28 Index 004 Part.-No. 01013409-GB (EU-BD 760/1)
17/84