1.01
Speed controller
IO Setup
F
¨
A Function (output 0-10 V)
1 A: Constant voltage 10 V
2 A: proportional modulation
3 A: proportional signal E1
4 A: proportional signal E2
5 A: Group control
¨
D1 / D2 Function (Digital Inputs)
1 D: Enable ON/OFF
2 D: External fault
3 D: Limit ON/OFF
4 D: Switch over: Signal E1 / E2
5 D: Switch over Set Intern 1 / 2
6 D: Switch over: Set intern / Set extern
¨
K1 / K2 Function (Relay out)
1 K: Operating indication
2 K: Fault indication
3 K: external fault
4 K: Limit modulation
5 K: Limit E1
6 K: Limit E2
8 K: Group control
Limits
¨
L
Function
(Limits)
1 L: Indication with centralized fault
2 L: Indication as Message
¨
E2 Function (Analog IN 2)
1E: switch over E1 / E2 by digital contact
4E: automatic control to higher value E1 or E2
(special functions with second signal)
8.2.5 Factory setting for mode
1.01
(preprogrammed) and user setting
Parameter
Factory
setting
User
Setting
Set Intern 1
80 %
Set Intern 2
--
Min. Speed
0 %
Max. Speed
100 %
Set external 1
ON
Setting
Mode
1.01
E1 Analog IN
0-10 V
E2 Function
OFF
E2 Analog IN
-----
B
ase set
u
p
PIN-Protection
OFF
Set protection
OFF
Save user Setup
OFF
Limit
-----
On Value Group2
-----
N min at Group2
-----
ControllerSetup
A Function
1 A
A min
0.0V
A max
10.0 V
A Inverting
OFF
D1 Function
OFF
D1 Inverting
--
D2 Function
OFF
D2 Inverting
--
E1 Inverting
OFF
E2 Inverting
-----
K1 Funktion
1 K
K1 Inverting
OFF
K2 Function
2 K
K2 Inverting
OFF
IO
Setup
BUS Address
247
Level Function
OFF
Level min.
-----
Level max.
-----
Level Delay
-----
Lmt E1Function
OFF
Lmt E1 min.
-----
Lmt E1 max.
-----
Lmt E1 Hyst.
-----
Lmt E1 Delay
-----
Lmt E2 Function
-----
Lmt E2 min.
-----
Lmt E2 max
-----
Lmt E2 Hyst.
-----
Limits
Lmt E2 Delay
-----
Cos Phi
0.80
Rampup time
20 sec.
Rampdown time
20 sec.
Suppression 1
OFF
Range 1 Min.
-----
Ragne 1 Max.
-----
Suppression 2
OFF
Range 2 Min
-----
Range 2 Max.
-----
Suppression 3
OFF
Range 3 Min
-----
Range 3 Max.
-----
M
o
tor Setu
p
Summary of Contents for Ucontrol PXDM Series
Page 80: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 80 105 ...
Page 92: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 92 105 ...
Page 96: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 96 105 ...
Page 100: ......