Handbook
Ucontrol
type-lines PXDM
Date 06/04
TBL02_55-GB06/04
Part.-No. 00153239-GB
Page 32 / 105
2
Example for programming mode
2.01
(temperature control)
For all modes in group 2 (
2.01
,
2.02
,
2.03
, ....)
E1 Analog
IN
factory setting at TF.. (KTY)
Alternative selection signal: 0-10 V, 0-20 mA, 4-20 mA, jumper accordingly inserted (Inverting
F
IO Setup).
The sensor measurement range must be entered in order to display the actual value correctly.
Example with a 0-10 V sensor and 0-100° C measurement range (proportional output signal):
Actual value for 0 V Sensor signal = 0° C (initial value measuring range)
Actual value at 10 V Sensor signal = 100° C (final value measuring range)
Input of the decimal places (depending upon measuring range)
Selection E1 display unit
E1 Offset
The ”OFFSET” function can be used for parallel shift of this linear characteristic. That is to say
the control unit then does not work with the real signal from the actual value but rather with a
signal increased or decreased by the value of the ”OFFSET”.
If at all possible, any sensor calibration should be performed with a calibrated comparison
measurement device.
Sensor calibration (Offset) E1, factory setting to 0 K.
↓
P
↑
ESC
↓
↑
↓
↑
Summary of Contents for Ucontrol PXDM Series
Page 80: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 80 105 ...
Page 92: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 92 105 ...
Page 96: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 96 105 ...
Page 100: ......