8.3.7 For mode
2.03
temperature controller with additional functions: temperature monitoring
Alarm message when over or falling below the adjusted temperature
If the set value for the minimum alarm is not reached or the set value for the maximum alarm is
exceeded, a message is generated via the alarm symbol in the display. In addition, „Lmt E1 min“ is
displayed alternately with the actual value for the minimum alarm and Lmt E1 max for the „Maximum
alarm“. An external message follows via the factory-assigned K1 relay.
Example for display if temperature is falling below setting „Alarm Minimum“
Relay K1 disengages (if not inverted)
Example for display if temperature is exceeding setting „Alarm Maximum“
Relay K1 disengages ( if not inverted)
↓
↑