Handbook
Ucontrol
type-lines PXDM
Date 06/04
TBL02_55-GB06/04
Part.-No. 00153239-GB
Page 49 / 105
IO Setup
F
¨
A Function (output 0-10 V)
1 A: constant voltage 10 V
2 A: proportional modulation
3 A: proportional signal E1
4 A: proportional signal E2
5 A: Group control
¨
D1 / D2 Function (digitale inputs)
1 D: Enable ON/OFF
2 D: External fault
3 D: Limit ON/OFF
4 D: Switch over: Signal E1 / E2
5 D: Switch ofer Setpoint 1 / 2
6 D: Switchover: Internal / External
7 D: Controlling /Manual internal
8 D: Switch over: actualValue>Set=n+/n-
¨
K1 /K2 Function (Relay out)
1 K: Operaiting indication
2 K: Fault indication
3 K: external fault
4 K: Limit modulation
5 K: Limit E1
6 K: Limit E2
7 K: Setpoint Offset
8 K: Group control
¨
E2 Function (Analog IN 2)
F
1 E: 0-10 V external Setpoint
2 E: external manual mode
3 E: Sensor average to E1
(only for mode 2.04 alternative)
4 E: Sensor comparison to E1
5 E: Sensor difference to E1
6 E: Sensor for Setpoint lowering
(only for Mode 4.02 and 5.02)
8.4.7 Factory setting and user setting for modes
3.01
..
3.04
Parameter
Factory setting
User
Setting
Setpoint 1
12.0
bar
25.0
°C
12.0
bar
25.0
°C
Setpoint 2
-----
-----
-----
-----
Pband
5.0 bar
5.0 K
5.0 bar
5.0 K
Min. Speed
0 %
0 %
0 %
0 %
Max. Speed
100 %
100 %
100 %
100 %
Manual mode
OFF
OFF
OFF
OFF
Speed manual
100 %
100 %
100 %
100 %
Setting
Mode
3.01
3.02
3.03
3.04
E1 Analog IN
2-25
DSF
2-25
DSF
2-25
DSF
2-25
DSF
E1 Refrigerant
-----
R 507
-----
R 507
E1 Min.
-----
-----
-----
------
E1 Max.
-----
------
------
------
E1 Decimal
-----
------
------
------
E1 unit
-----
------
------
------
E1 Offset
0.0 bar
0.0 K
0.0 bar
0 K
E2 Function
OFF
OFF
4E
4E
E2 Analog IN
------
-----
2-25
DSF
2-25
DSF
E2 Refrigerant
-----
-----
-----
R507
E2 Min.
-----
-----
-----
-----
E2 Max.
-----
-----
-----
------
E2 Decimal
------
-----
-----
------
E2 unit
-----
------
------
------
E2 Offset
-----
------
0.0 bar
0 K
B
ase set
u
p
PIN-Protection
OFF
OFF
OFF
OFF
Set Protection
OFF
OFF
OFF
OFF
Save user Setup
OFF
OFF
OFF
OFF
Alarm Sensors
OFF
OFF
OFF
OFF
Limit
-----
------
------
------
Msco
OFF
OFF
OFF
OFF
ON value Group2
-----
------
------
------
n-min atGroup2
-----
-----
-----
-----
actVal > Set = n+
ON
ON
ON
ON
Type of control
P
P
P
P
KP
50 %
50 %
50 %
50 %
KI
50 %
50 %
50 %
50 %
KD
50 %
50 %
50 %
50 %
TI
0 %
0 %
0 %
0 %
Controlle
r Se
tup
A Function
1 A
1 A
1 A
1 A
A min
0.0 V
0.0 V
0.0 V
0.0 V
A max
10.0 V
10.0 V
10.0 V
10.0 V
A Inverting
OFF
OFF
OFF
OFF
D1 Function
OFF
OFF
OFF
OFF
D1 Inverting
-----
-----
-----
-----
D2 Function
OFF
OFF
OFF
OFF
D2 Inverting
-----
-----
-----
-----
E1 Inverting
OFF
OFF
OFF
OFF
E2 Inverting
-----
-----
-----
-----
K1 Function
1 K
1 K
1 K
1 K
K1 Inverting
OFF
OFF
OFF
OFF
K2 Function
2 K
2 K
2 K
2 K
K2 Inverting
OFF
OFF
OFF
OFF
BUS Address
247
247
247
247
IO
Setup
3.01
Pressure control condensers
- Setpoint in bar
3.02
Pressure control for condensers with
input for refrigerant
- Setpoint in °C
3.03
2 sensors for dual circuit condensser
-
regulation to the highest actual
value
(selction amplifier integrated).
- Setpoint in bar
3.04
t w o sensors for dual circuit
condenser with input for refrigerant
-automatic regulation to the highest
pressure (selection amplifier)
- Setpoint in °C ,
- also for different refrigerants suitably
there comparison of the
temperatures