Handbook
Ucontrol
type-lines PXDM
Date 06/04
TBL02_55-GB06/04
Part.-No. 00153239-GB
Page 51 / 105
8.5 Pressure control for ventilation systems
4.01
, setpoint depending on outdoor temperature
4.02
8.5.1 Basic setting
4.01
and
4.02
1
Place the internal plug (jumper) for the external default signal in the correct position. Caution – not under voltage!
Observe the safety notices!
2
Switch the voltage on and select mode of operation (general controller function) factory setting
1.01
= speed controller.
If necessary configuration of sensors.
1
Type of signal Input Analog IN 1
INFO
0-10 V
No PINs with
jumper bridged
Factory setting for pressure sensors with 0-10 V
signal proportional to measuring range
e. g. Ziehl-Abegg sensors DSG..
0-20 mA /
4-20 mA
Lower PINs with
jumper bridged
Pressure sensors 0-20 mA or 4-20 mA proportional to
measuring range
Connection for pressure sensor type DSG..at „Analog IN 1“
Input 2 is automatically activated upon selection of operating mode with 2-sensors
4.02
. The jumpers E 2.1 (J2) and E 2.2
(J3) must be inserted in accordance with the sensor signal.
Passive Temperature sensor type KTY10-6
For Ziehl-Abegg Sensors TF.. put in up position
TF..
(KTY10-6)
Upper PINs
with Jumper
bridged
Passive Temperature sensor type KTY10-6
For Ziehl-Abegg Sensors TF.. put in up position
for active sensors as for sensor at E1
for sensors type TF.. at „Analog IN 2“
J4 J5
E1.1 E1.2
J4 J5
E1.1 E1.2
Sensor DSG..
(0-10 V)
E1
24V
GND
br ge ws
BN YE WH
DSG..
Sensor TF..
KTY10-6
(KTY11-2a)
GND
E2
υ
J2 J3
E2.1 E2.2
Summary of Contents for Ucontrol PXDM Series
Page 80: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 80 105 ...
Page 92: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 92 105 ...
Page 96: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 96 105 ...
Page 100: ......