8.6 Volume control (constant) air conditioning
5.01
, depending on outdoor temperature
5.02
8.6.1 Basic setting
5.01
and
5.02
1
Place the internal plug (jumper) for the external default signal in the correct position. Caution – not under vpltage!
Observe the safety notices!
2
Switch the voltage on and select mode of operation (general controller function) factory setting
1.01
= speed controller.
If necessary configuration of sensors.
1
Type of
signal
Input Analog IN 1
INFO
0-10 V
No PINs with
jumper bridged
Factory setting for pressure sensors with 0-10 V signal
proportional to measuring range
e. g. Ziehl-Abegg sensors DSG..
0-20 mA /
4-20 mA
Lower PINs
with jumper
bridged
Pressure sensors 0-20 mA or 4-20 mA proportional to
measuring range
Connection for pressure sensor type DSG..at „Analog IN 1“
Input 2 is automatically activated upon selection of operating mode with 2-sensors
5.02
. The jumpers E 2.1 (J2) and E 2.2
(J3) must be inserted in accordance with the sensor signal.
TF..
(KTY10-6)
Upper PINs
with Jumper
bridged
Passive Temperature sensor type KTY10-6
For Ziehl-Abegg Sensors TF.. put in up position
for active sensors as for sensor at E1
for sensors type TF.. at „Analog IN 2“
J4 J5
E1.1 E1.2
J4 J5
E1.1 E1.2
Sensor DSG..
(0-10 V)
E1
24V
GND
br ge ws
BN YE WH
DSG..
Sensor TF..
KTY10-6
(KTY11-2a)
GND
E2
υ
J2 J3
E2.1 E2.2