10.2.5 Set Intern 1 / Set Intern 2 or. Setpoint 1/2 Function 5D
¨
Switch over between Set Intern 1 and Set Intern 2
(for speed controller
1.01
)
Operation with “Internal default 2“ is signalized by the moon symbol for reduced operation.
“Set external 1“ under settings must be programmed to OFF
contact at digital input e. g. Digital IN 1 = D1-D1
Set Intern 1 at opened contact
↔
Set Intern 2 at closed contact
D1 Inverting OFF
Set Intern 1 at closed contact
↔
Set Intern 2 at closed contact
D1 Inverting ON
¨
Switch over between Setpoint 1 and Setpoint 2
(for modes as controller higher
2.01
)
operation with „Setpoint 2“ is signalized by the moon symbol for reduced operation.
contact at digital input e. g. Digital IN 1 = D1-D1
Setpoint 1 = 18° C at opened contact
↔
Setpoint 2 = 25° C at closed contact
D1 Inverting OFF
Setpoint 1 = 18° C at closed contact
↔
Setpoint 2 = 25° C at opened contact
D1 Inverting ON
Controller
3~ 400 V
D1 D1
0 1
3~ 0-100 %
Sensor
Controller
3~ 400 V
3~ 78 % = Intern 1
D1 D1
0 1
0
1
3~ 40 % = Intern 2