Handbook
Ucontrol
type-lines PXDM
Date 06/04
TBL02_55-GB06/04
Part.-No. 00153239-GB
Page 9 / 105
¡
Line voltage 3~ 208 ... 400 V (-15 % / +10 %), 50/60 Hz
¡
Stepless controlled output voltage approx. 20-100 % (line voltage)
¡
Min. motor current 0.2 A for PXDM5, PXDM5 / 0.5 A for PXDM10/15/25/35...
¡
Input resistance for sensor or signal set for the rotational speed:
- For 0-10 V input: Ri
>
100 k
W
- For 4-20 mA input: Ri = 100
W
¡
Voltage supply e.g. for s24 V ±20 %, I
max
120 mA
¡
Output (0-) 10 V, I
max
10 mA (short-circuit-proof)
¡
Max. permissible ambient temperature 40° C (up to 55° C with derating)
¡
Min. permissible ambient temperature 0° C (
if mains voltage is not switched off up to -
20°C)
¡
Permissible rel. humidity 85 % no condensation
¡
Interference emission EN 50081-1
¡
Interference immunity EN 61000-6-2
¡
Harmonics current EN 61000-3-2
The units comply with EN 61000-3-2 for a "professional unit". Up to a maximum current of
4 ampere the limits were complied without any qualification.
3.3 Versions Ucontrol
Housing version IP54 for wall mounting
¨
PXDM..A
internal LCD-Multifunction display with plain language text
¨
PXDM..
external terminal type AXG-1A(E), for start-up and setting necessary
IP20 for switch cabinet mounting (semiconductor fuses must be installed in supply by client)
¨
PXDM..AE
internal LCD-Multifunction display with plain language text
¨
PXDM..E
external terminal type AXG-1A(E), for start-up and setting necessary
Summary of Contents for Ucontrol PXDM Series
Page 80: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 80 105 ...
Page 92: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 92 105 ...
Page 96: ...Handbook Ucontrol type lines PXDM Date 06 04 TBL02_55 GB06 04 Part No 00153239 GB Page 96 105 ...
Page 100: ......