MU1001K
12370-0707-01
Seite
5 / 12
www.ziehl.de
Observe the maximum temperature permissible when installing in switching cabinet. Make sure
sufficient space to other equipment or heat sources. If the cooling becomes more difficult e.g.
through close proximity of apparatus with elevated surface temperature or hindrance of the cooling
air, the tolerable environmental temperature is diminishing.
Attention!
All wires connected to the device must have insulation rated at least 300 Vac.
6
Commissioning
6.1 Overview of commissioning
The MU1001K can be commissioned to predefined standard ranges or scaled to an arbitrary range.
There are two different ways to do the settings:
Point 6.2
– 6.4: MU1001K setting a predefined range
Point 6.5
– 6.7: MU1001K scaling an arbitrary range
6.2 Overview of the predefined standard ranges
Following standard ranges can be set without adjustment to the unit:
Input (300 V)
Input (10 V)
Output (mV)
Zero point
Full scale
Zero point
Full scale
Zero point
Full scale
0 V …
20 V
0 V …
10 V
0 mV …
60 mV
0 V …
50 V
2 V …
10 V
0 mV …
150 mV
0 V …
100 V
-
10 V …
10 V
0 mV …
300 mV
0 V …
200 V
-
60 mV …
60 mV
0 V …
300 V
-
150 mV …
150 mV
-
300 mV …
300 mV