Aplication and short description 

 

Temperature-Relays TR 111 V can be used as limit-switches or 2-point controllers with high 
repeat accuracy. 
3 measuring-ranges, adjustable hysteresis and switching delay and the choice between 
operating- and closed-current principle of the relay make it a very universal device. 
Protection from over-temperature in processes, plants and machines.  
Monitoring of temperatures in bearings. 
Controlling of temperatures in processes and plants. 

 

Overview

 of 

functions

 

   

 

 

Measuring input 1x Pt 100 (RTD) / 2-wire 

 

3 or 4 measuring-ranges switchable 

 

1 limit adjustable 0...100 % 

 

switching delay adjustable 0,1...10 s 

 

Output-relay 1 changeover-contact (co) 

 

Operating- or closed-current-tprinciple selectable 
with bridge 

 

Switching off at sensor-shortcircuit or break 

 

LEDs for display state of operation 

 

Housing for mounting in switchgear cabinets or 
fuseboxes, 35 mm wide 

 

Mounting heigt 55 mm 

 
 
 
 
 
 
 

Display and operating elements

 

 

Potentiometer for limit value 

LED Power 

Hysteresis 

LED Relay on 

Switching delay don/doff 

Range selection 

 
 

Connection plan 

 

 

Summary of Contents for Pt 100

Page 1: ...o KG Daimlerstr 13 D 74523 Schwäbisch Hall Tel 49 791 504 0 Fax 56 e mail info ziehl de Operating manual Pt 100 Temperature Relay TR 111 V MINIPAN digital panel meters temperature and mains controlling special purpose instruments for customer requirements www ziehl com Archive document www ziehl de ...

Page 2: ...erature in processes plants and machines Monitoring of temperatures in bearings Controlling of temperatures in processes and plants Overview of functions Measuring input 1x Pt 100 RTD 2 wire 3 or 4 measuring ranges switchable 1 limit adjustable 0 100 switching delay adjustable 0 1 10 s Output relay 1 changeover contact co Operating or closed current tprinciple selectable with bridge Switching off ...

Page 3: ...ple If a temperature sensor is connected the installed relay picks up 11 14 closed ok The relay releases in the case of a sensor breakdown The thermostat signals and switches when the set limit is exceeded If the temperature at the sensor rises over the adjusted value then the relay releases The switching status is signalled by a LED relay picked up LED on At operating current principle the functi...

Page 4: ...ructions may lead to death physical injury or damage of the equipment itself and of other apparatus and equipment If in any case the information in the instructions manual is not sufficient please contact our company or the responsible representative Instead of the industrial norms and regulations written in this instructions manual valid for Europe you must observe out of their geographical scope...

Page 5: ...Error of setting 5 K Temperature dependence 0 05 K Hysteresis adjustable app 2 10 K Switching delay don doff adjustable 0 1 s 10 s Relay output 1 change over contact co Switching voltage max AC 250 V Switching current max 5 A Switching power AC cos 1 max 1250 VA ohmic load max 48 W at DC 24 V Derating factor at cos 0 7 0 5 Rated operational current AC 15 Ie 2 A Ue 250 V Rated operational current D...

Page 6: ...ted ferrules 1 x 2 5 mm2 Protection class housing IP 30 Protection class terminals IP 20 Attachment Mounting 35 mm standard rail according to EN 60715 Optional Screw mounting M4 Weight approx 130 g Subject to technical modifications Form V2 Dimensions in mm 1 Oberteil cover 2 Unterteil base 3 Riegel bar for snap mounting 4 Plombenlasche latch for sealing 5 Frontplatteneinsatz front panel 6 Kennzei...