Power supply units can be used at any (sensible) position in the RS485 BUS. The plus lines of these power
supply units should not be connected to each other.
Example:
6.2 Ethernet
Ethernet socket for network cables
7
Detailed Description
[Menu item / parameters]
on the device
7.1 Extraction on relay K1
Switching on the extraction system:
➢
A machine is switched on
➢
After delay time for machine
➢
The slider / flap of the extraction channel opens
➢
After delay time for extraction
Switches on the extraction system
Machine / I limit value]
exceeded
[Machine / Delay on]
[Extraction / Delay on]
Switching off the extraction system:
➢
Last machine is switched off
➢
After delay time for machine
➢
After delay time for extraction
➢
Switches off the extraction system
➢
After delay time (machine, last overrun)
➢
The slider / flap of the extraction channel closes
[Machine / I-limit value]
undershot
[Machine / Overrun time]
[Extraction / Overrun time]
[Machine / last overrun]