STW164IP
12660-0710-00
Page
21 / 30
www.ziehl.de
10.6.5 Relays
On the device, Menu
/ Relay
In the Web Browser,
Register Configuration,
Relay
Parameter, description
Discharge
from / relay K3 / relay
K4
Not possible. (see
Discharge)
Discharge function:
-> if necessary, parameterize to a relay
Volume flow >>
off / Relay K3 / Relay
K4
Volume flow exceeded
off /
Rel K4 / Rel K3
Message volume flow exceeded:
-> if necessary, parameterize to a relay
End position error
off / Relay K3 /
Relay K4
End position error
off / Rel
K4 / Rel K3
Message end position error (only with activated function
"End position Y4"):
-> if necessary, parameterize to a relay
(End position of "slider open" not reached within the
parameterized time)
Fault
off / Relay K3 / Relay
K4
Fault
off / Rel K4 / Rel K3
Reporting faults/errors,
- Error from RS485 BUS (device not reachable)
- Error Us 24V from STW164IP
- Error in internal memory
- Error in parameter
- Error in parameter for priority of slider
- Internal device error
- Error Us 24V from STW164IP
- Display error
-> if necessary, parameterize to a relay
10.6.6 Analog Output
On the device, Menu
/ Analog Output
In the web browser,
Register Configuration,
Analog Output
Parameter, description
U at 0% volume
0.0....10V
U at 0% volume
0.0....10V
Output voltage at 0% volume flow.
When the extraction is switched off (relay K2 off), the
output voltage is always 0V
10V @ volume
0...100%
10V @ volume
0...100%
Volume flow at DC 10V output voltage