10.6.2 Extraction
On the device, Menu
/ Extraction
In the web browser, Register
Configuration, Extraction -
Relay K1
Parameter, description
Delay on,
00:00.....20:00
mm:ss
Delay on,
0.....1200s
The start of the extraction is delayed by this time
Overrun time
00:00.....20:00
mm:ss
Overrun time
0.....1200s
The shutdown of the extraction is delayed by this time
Min. Vol.
1.100%
Min. volume flow
1,100%
Minimum volume flow of the entire system. To achieve
this, additional valves/flaps are opened if necessary
Max Vol.
5.100%
Max. volume flow
5.100%
Maximum permissible volume flow of the entire system. If
exceeded, an error message is displayed on the device/in
the web browser. This message can be parameterized to
a relay (see relay)
Open more
yes / no
Open more sliders
yes / no
Setting whether after exceeding the max.
volume flow, more sliders/flaps may open
Min. vol line
1.4
1.100%
Min. volume flow line
1.4
1.100%
Minimum volume flow in the respective extraction line. In
order to achieve this, additional sliders/flaps in the line
may be opened