STW164IP
12660-0710-00
Page
20 / 30
www.ziehl.de
10.6.3 Cleaning
On the device, Menu
/
Cleaning
In the web browser,
Register Configuration,
Cleaning - Relay K2
Parameter, description
Addition
time 00:01......20:00
hh:mm
Addition time
1......1200min
Time after which the filters are cleaned (time at 100%
volume flow)
Rundown time
00:00.....20:00
mm:ss
Rundown time after K1
0.1200 s
Delay time after switching off the extraction until cleaning
begins
Vibration
Static/Compressed
Air / 0.1.....10s
Vibration
Static/compressed air/pulse
0.1.....10s
Cleaning type:
Compressed air: Relay K2 on for 1s (starts external
compressed air cleaning)
Static: Relay K2 statically on during cleaning 0.1.....10.0s
(pulse): Relay pulses with set duration during cleaning
Vibration intervals
0.....20
Number of vibration intervals
0.....20
Number of vibration intervals, which are composed of
interval vibration time and interval break time
Vibration time
1.....30s
Interval vibration time
1.....30s
On cleaning time (K2 on, in case of pulse vibration K2 =
on/off in alternation) during the vibration intervals
Break time
00:00.....02:00
mm:ss
Interval break time
1....120s
Off cleaning time (K2 off) during the vibration intervals
Continuous vibration
time
00:00....20:00 mm:ss
Continuous vibration time
0.....1200s
The continuous vibration time starts after the vibration
intervals.
Static vibration:
K2 = on
Pulse vibration:
K2 = on/off in alternation
Input Y2
cleaning / 1.....100%
Input Y2
cleaning /
1.....100%
Cleaning: The addition time is set to 0, cleaning takes
place at the next possible time. 1....100% Cleaning is
suppressed or aborted. The set volume flow is counted
towards the addition time
10.6.4 Discharge
On the device, Menu
/ Discharge
In the web browser,
Register Configuration,
Discharge
Parameter, description
Not possible... (see
relay)
Discharge
from / Rel K4 /
Rel K3
Parameterize the function of the discharge to a relay
Starts with
cleaning / extraction
Start condition
when
cleaning is pending / when
extraction on
Cleaning:
- starts when the addition time has
elapsed (= 0)
- ends when cleaning is completed and the
subsequent overrun time has elapsed
Extraction: - starts when at least one slider is open
- ends when cleaning is completed and the
subsequent overrun time has elapsed, or
when the extraction has ended and the
subsequent overrun time has elapsed
Overrun time
00:00.....20:00
mm:ss
Overrun time
0...1200s
Overrun time of the discharge starts as soon as the
condition for the discharge is no longer met.