STWA1  

12050-0701-00

  

Page

 

3 / 4 

www.ziehl.de 

  

Connecting diagram 

See operating manual of ZIEHL current relays type STW. 
 
 
 

Attention! 
There may only one conductor be lead through the transformer!  
 
 

 

Attention! 
The connecting cable can be extended up to 50 m. When laying parallel to 
power cables use twisted or shielded cables.

 

 

 
 

Attention! 
The polarity of the current transformer output (white marking on the cable) must be  
observed only if several current transformers are connected in series to increase the  
sensitivity. 

 
 
 

5.1  Tips 

Limit too high

 (current in wire too low): 

  Loop through wire several times

 

 

Limit too low

 (small loads shall not be recognized) 

  Connect a resistor (0,25 W / 200 V) in parallel to the current transformer STWA1(H)

  

  -  - resistor 750 Ohm = enhancement by factor 2x 

  -  - resistor 330 Ohm = enhancement by factor 4x 

  -  - resistor 150 Ohm = enhancement by factor 10x 

Because of high tolerances we recommend to determine the best value by try out. 

 

 

Technical data 

 

Input / primary conductor 

 

 

 

Rated thermal continuous current Icth 

AC 100 A 

Thermal rated short-time current Ith 

AC 300 A for 10 s 

 

 

Rated frequency  

50/60 Hz 

Max. Operating voltage Um 

0.72 kV 

 

Output 

 

 

 

Max. output voltage U at Icth = 100 A 

200 V peak (not limited) 

Max. short circuit current I at Icth = 100 A 

140 mA eff. 

 

Test Conditions 

EN 61010-1 

Type test voltage 

AC 2500 V 50 Hz 60 s 

 

Installation conditions 

 

Permissible ambient temperature 

-25 °C ... +70 °C 

Summary of Contents for STWA1

Page 1: ... 3 5 1 Tips 3 6 Technical data 3 7 Housing 4 1 Application and short description Current transformers STWA1 are inductive working single ended current transformers Due to the applied measuring principle these current transformers are only suitable for alternating current The current transformer STWA1 is used together with ZIEHL current relay type STW for current detection and control of extraction...

Page 2: ...phical scope the valid and relevant regulations of the corresponding country DANGER Hazardous voltage Will cause death or serious injury Turn off and lock out all power supplying this device before working on this device DANGER In a non loaded open secondary circuit of the current transformer STWA1 high voltages are induced at the secondary terminals For primary currents 16 A this voltage can be d...

Page 3: ...Limit too low small loads shall not be recognized Connect a resistor 0 25 W 200 V in parallel to the current transformer STWA1 H resistor 750 Ohm enhancement by factor 2x resistor 330 Ohm enhancement by factor 4x resistor 150 Ohm enhancement by factor 10x Because of high tolerances we recommend to determine the best value by try out 6 Technical data Input primary conductor Rated thermal continuous...

Page 4: ...100 Hz 1 g 2 25 Hz 1 6 mm 25 150 Hz 5 g Housing clip on Housing material Polyamide PA66 blue Flammability UL94 V 2 Grouting 2 component silicon RTV627 Protection class IP 20 Outside diameter 31 3 mm Height 18 mm Connection cable Wire LiYv 7x 0 25 0 34 mm AWG 22 black Wirelength 2 x 1000 mm Stripping length 10 mm Opening for primary conductor 11 mm Mounting position any Weight 43 g Subject to techn...

Reviews: