SW32V
11820-0701-01
Page
4 / 22
www.ziehl.de
2
Factory settings and software version
When changing programs, all parameters are reset to the factory settings.
Menu
Parameter / Unit
Default settings
Users Data
3AC+N
3AC
1AC
DC
3AC+N
3AC
Pr1
Pr2
Pr3
Pr4
Pr5
Pr6
A1,
A1,
(Alarm)
on
on
on
on
on
on
U1,
(upper limit)
V
253
440
253
242
264
115
H1,
(Hysteresis)
V
5.0
5.0
5.0
5.0
3.0
1.0
dal
(Alarm delay)
s
0.10
0.10
0.10
0.10
0.10
0.10
dof
(Reset delay)
s
0
0
0
0
60
60
A1_
A1_
(Alarm)
on
on
on
on
oFF
off
U1_
(lower limit)
V
196
340
196
198
104
45.0
H1_
(Hysteresis)
V
5.0
5.0
5.0
5.0
2.0
1.0
dal
(Alarm delay)
s
0.10
0.10
0.10
0.10
0.30
0.30
dof
(Reset delay)
s
0
0
0
0
60
60
A1
asy
(Asymmetry)
%
off
off
off
off
dal
(Alarm delay)
s
0.10
0.10
0.10
0.10
Phf
(Phase sequence)
off
off
off
off
rel
(Relay function)
r
r
r
r
r
r
A2,
A2,
(Alarm)
on
on
on
on
on
on
U2,
(upper limit)
V
253
440
253
242
249
108
H2,
(Hysteresis)
V
5.0
5.0
5.0
5.0
3.0
1.0
dal
(Alarm delay)
s
0.10
0.10
0.10
0.10
60.0
60.0
dof
(Reset delay)
s
0
0
0
0
60
60
A2_
A2_
(Alarm)
on
on
on
on
on
on
U2_
(lower limit)
V
196
340
196
198
184
80.0
H2_
(Hysteresis)
V
5.0
5.0
5.0
5.0
3.0
1.0
dal
(Alarm delay)
s
0.10
0.10
0.10
0.10
2.70
2.70
dof
(Reset delay)
s
0
0
0
0
60
60
A2
asy
(Asymmetry)
%
off
off
off
off
dal
(Alarm delay)
s
0.10
0.10
0.10
0.10
Phf
(Phase sequence)
off
off
off
off
rel
(Relay function)
r
r
r
r
r
r
ddi
ddi
(Display delay)
s
0.5
0.5
0.5
0.5
0.5
0.5
dit
(Display duration)
s
3.5
3.5
3.5
3.5
Si
U
(Voltage)
V
230
400
230
220
230
100
Cod
On
/
off
off
off
off
off
off
off
pin
(Pin code)
504
504
504
504
504
504
Inf
fnr
Firmware version
_13
_13
_13
_13
_13
_13
snr
Serial number
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
xxxxx
Pr
Program
1
2
3
4
5
6
Display the program
: Press the "Set" key for 4 s in the display mode.
Display the software version
: Press the "Set" key for 10 s in the display mode.