ZGR TOWER PRO 6 10 KVA
Operation manual
www.zigor.com
25
Operation Output voltage setting (OPV)
Fig. 4-13 Output voltage setting
When under setting mode, press DOWN or when under frequency setting press UP, it goes to the output voltage
setting. The output voltage line flashes as in above picture (Fig. 4-13).
•
Use button ENTER/ON to choose a different output voltage. There are 4 different voltages: 208,220, 230
or 240.
•
Press ESC/OFF button to exit the output voltage setting and save the output voltage setting. Then go to
mode setting or frequency setting.
NOTE: When inverter is ON, it is necessary to turn off the inverter before setting voltage and frequency level.
Operation Output frequency setting (OPF)
Fig. 4-14 Frequency setting
When under the output voltage setting press DOWN or when under battery capacity setting press UP, it goes to
the frequency setting. The frequency line flashes as in above picture (Fig. 4-14).
•
Use button ENTER/ON to choose the different frequency. There are 2 different frequency: 50 / 60Hz.
•
Press ESC/OFF button to exit the frequency setting (save the frequency setting) and goes to output
voltage setting or battery capacity setting.
NOTE: When inverter is ON, it is necessary to turn off the inverter before setting voltage and frequency level.
Battery capacity setting (bAH)
Fig. 4-15 Battery capacity setting