ZGR TOWER PRO 6 10 KVA
Operation manual
www.zigor.com
11
3
INSTALLATION
3.1
Reception of material
Remove the UPS from the packaging and carry out a visual examination in order to detect any damage that might
have occurred during transport. Notify the seller about any damage.
List and check all the items indicated on the delivery note. Check that the material delivered corresponds with the
delivery note. Check the manufacturer´s identification plates located on the rear or side of the UPS.
3.2
Installation conditions
The place chosen for the installation must meet the following characteristics:
•
Protection against dust.
•
Protection against excessive humidity and heat sources.
•
Protection against atmospheric agents.
•
Avoid exposure to corrosive gases and agents.
•
Temperature of operating atmosphere b20º C and +25º C.
•
Easy connections.
•
Proximity to magnetic fields and high-power lamps must be avoided.
•
Prevent the UPS being exposed to the sun.
•
Do not obstruct the vents as this would prevent the correct dissipation of the heat produced by the UPS.
The minimum distance from the ventilation grills to walls or other obstacles must be 300mm.
•
Should the equipment not be installed immediately it must be stored in a room so as to protect it against
excessive humidity and or heat sources.
•
The highest altitude that UPS may work normally with full load is 1500 meters. The load capacity should
be reduced when this UPS is installed in place whose altitude is higher than 1500 meters, shown as the
Table 3-1:
(Load coefficient equals max load in high altitude place divided by nominal power of the UPS
)
ALTITUDE (m)
1500
2000
2500
3000
3500
4000
4500
5000
LOAD COEFICIENT
100%
95 %
90 %
85 %
80 %
75 %
70 %
65 %
Table 3-1 Load coefficient
No claims will be accepted if, 24 hours following the delivery of the goods, no notification of reception of
material in bad conditions has been received and if this circumstance is not notified to the forwarding agent at
the time of delivery.
WARNING
The UPS contains lead batteries that are charged when they leave the factory.
They can be stored for up to two years provided that they are recharged on a periodic basis, at least every six
months, during storage.