SR981S/SR982S operation manual of solar pump station
Page 57 of 85
temperature, and then function is deactivated.
Setup steps:
To select submenu DVWG, “DVWG ---” shows on the
screen. Default set is “OFF”.
►Press “SET” button, parameter “---” blinks on the screen.
►Press “SET” button to activate this function, and then “DVWG 70
o
C” shows on the
screen.
►Press “ ” button to adjust temperature of anti legionnaires’ function, adjustable
range: 5
o
C ~ 95
o
C.
►Press “ESC” button to exit the menu or wait for 20 seconds to exit automatically,
parameters are saved automatically.
8.5.2 SFB Switch-on/off of the solid fuel boiler
Example: (system 1) under the status that solid fuel boiler is enabled,
When tank temperature T3 drops below the switch-on temperature of solid fuel boiler
(SFON), and temperature of solid fuel boiler (T5) is between its minimum and
maximum temperature( MIN 3 and MAX3)
,
then solid fuel boiler R2 is triggered; when
tank temperature T3 rises up to the switch-off temperature of solid fuel boiler (SFOF),
or when temperature of solid fuel boiler (T5
)
exceeds the scope of its “MIN3” and
“MAX3”, then solid fuel boiler is ceased.
Note:
The
value of “MIN3” should be minimum 1
o
C higher than value of “SFOF”, for
example, when “SFON” is 50
o
C, “SFOF” is 55
o
C, and then “MIN3” must be “56
o
C” at
least, then when tank temperature is below 50
o
C, solid fuel boiler starts to run until
tank temperature rises up to 55
o
C, then solid fuel boiler stops to run.
Select “SFB” menu, “SFB” displays on the screen.
►Press “SET” button to enter menu, “SFB OFF” displays
on the screen.
►Press “SET” button again, “OFF” blinks; default set is
“OFF”
►Press “SET” button to enable this function, “SFB ON” shows on the screen.
►Press “ESC” button to exit the menu or wait for 20 seconds to exit, parameters are