28 | Operations Manual
9. To start charging the batteries set SOC to 50% so that the positive current would start to flow.
10. Acquire the Point 2. For Measured Value input the value from multimeter and press read to input the
display value.
11. Calculate and setup new K/B values by clicking Calc and Setup.
12. Check that the new values are set by clicking read next to original K/B values. The values should be the
same as the calculated values from step 11.
13. Repeat steps 8-12 until the measured and displayed current values are as accurate as possible.
14. This is the end of calibration for “Charge current”.
15. Select Calibration Type to be “Discharge Current”.
16. Repeat steps 6 to 8.
17. Start discharging the batteries, so that the negative current would start to flow.
18. Repeat steps 10 to 13. This is the end of calibration for “Discharge Current”
19. Continue calibration with current shunt. Select “Shunt (2)” under the Current Sensor Type. Select Current
Sensor Range to be 1200. Click set.
20. Repeat steps 5 to 18.
21. Finish calibration by selecting “Hall Sensor 1, Shunt (3)” under the Current Sensor Type. Select Current
Sensor Range to be 1200. Click set.