15 | UPStealth® 2 User Manual
Digital and DC Power Interconnect Cable
A1 - GND
A2 - B
Pins:
1. Can Bus (H)
2. Isolated CAN Bus GND
3. Can Bus (L)
4. 5V
5. Power Fail
~ 48Vdc
Communications and I/O
1. Connect to the ethernet port of the UPS (If being used. Ethernet cable is not provided by ZincFive).
2. Connect to the desired RELAY CONTACT TERMINAL(S) on the UPS (If being used. Wiring is not provided by
ZincFive). The relay connection are CLASS 2.
Connecting Battery Panel or Battery Module to UPS and PIM
ONLY ZincFive batteries may be used with the UPS. Please refer to the UPS Overview for certified batteries.
To connect the battery to the UPS, follow these steps:
1. Connect the UPStealth 2 Battery Panel or Battery Module BATTERY OUTPUT to the BATTERY INPUT of the UPStealth 2
UPS 1000W via the provided Digital and DC Power Interconnect Cable.
Note: If the Cold Start button is pressed upon connecting the Battery to the UPS, do not connect or disconnect
the Battery to or from the UPS until the green LED is off and Cold Start has expired. Press the Cold Start button
for 10 seconds to turn off the system.
2. Connect the
UPStealth 2 Battery Panel or Battery Module
AC INPUT to the TO BATTERY AC IN on the PIM using the
supplied AC Power Interconnect Cable and AC Power Daisy Chain Cable as needed. When the battery unit is
connected to AC the battery unit LED should:
•
White Blinking = Battery at rest
•
Blue = Charging Mode
ONLY use the ZincFive provided interconnect cable