UPStealth® 2 User Manual | 40
STATUS
SETTINGS
POWER FAIL THRESHOLDS
SET ENHANCED SENSITIVITY
Description:
Use this screen to configure the sensitivity to utility power quality before the UPStealth 2 UPS 1000W will switch to battery power.
On The Display:
•
ENHANCED SENSITIVITY:
Allows you to increase the sensitivity to variance of the utility waveform before the UPStealth 2 will
switch to battery power. Your choices are ON or OFF. Turn the Navigation Dial to turn ON or OFF enhanced sensitivity and then
press the dial to set the value. OFF sensitivity is selected by default.
•
Press the BACK button when you are finished configuring this value.
Notes:
•
OFF allows the most variance from ideal waveforms and is most appropriate for situations where signal cabinets are located
near known generators of utility power noise, such as large HVAC units or intersections under construction.
•
Select ON if your signal equipment requires additional protection.
•
Select OFF if your UPStealth 2 is switching to battery power more often than seems reasonable.
Set Sensitivity
Summary of Contents for UPStealth 2
Page 2: ......
Page 71: ...UPStealth 2 User Manual 68 Notes ...
Page 72: ...69 UPStealth 2 User Manual Notes ...
Page 73: ......