41 | UPStealth® 2 User Manual
STATUS
SETTINGS
POWER FAIL THRESHOLDS
LINE QUALIFY TIME
Description:
Use this screen to configure the amount of time that utility power must be within power quality parameters before the unit
switches from battery power back to utility power. This time may protect your equipment from rapid power cycling, noisy power,
or power frequency mismatches after a utility power failure.
On The Display:
•
SECONDS:
Allows you to select the time period, in seconds, that the utility power must be within quality parameters before
the UPStealth 2 switches from battery power to utility power. Your choices are 3, 10, or 30 seconds. Turn the Navigation Dial to
select the line qualify time and then press the dial to set the value. 30 seconds is selected by default.
•
Press the BACK button when you have selected this value.
Set Line Qualify Time