EN54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
470R
(nominal)
470R
(nominal)
470R
(nominal)
470R
(nominal)
+
+
-
-
MCP
MCP
Main PCB Zone
Input Terminations
Main PCB Zone
Input Terminations
Refer to Section 6.4.1 for details on standby battery sizes
and maximum number of zones.
Note:
This method is not recommended for new
installations.
Refer to Section 6.4.1 for details on standby battery sizes
and maximum number of zones.
Capacitor:
Use 0.47µF.
Capacitor:
Use 0.47µF.
4k7
Schottky diode bases can be used.
Schottky diode bases can be used.
Method 2:
Supports new and existing installations using Active End-
of-Line (AEOL) - (ZIRCON/EN/CAPKIT). For the AEOL
to function correctly an additional 10µF stabilising
capacitor must be fitted across the zone terminals (not
supplied).
Method 3
Supports existing installations where there is a 4K7 resistor
EOL fitted already and it is preferable to install the panel
without modifying the existing wiring. Call points must be
wired nearer to the panel than detectors.