997-532-000-1, Issue 1
March 2006
32
EN54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
7.9
Configuration Examples
The following examples are provided to offer guidance
when navigating through some of the menu options.
Note:
If you lose your way at any time, simply press the ‘main
menu’ pushbutton
to return to the menu select
position.
Example 1
How do I configure the panel back to the factory default
state?
Ensuring that the panel is at access Level 3 (refer to
earlier in this section). Use the icons in brackets (located
above each pushbutton) when proceeding:
Press the following pushbuttons in the order shown:
- Selects Miscellaneous option
- Selects Configuration sub-item menu
(hold for 5 seconds) - System LED 2 lights to
indicate the factory default condition has been restored.
Press the
pushbutton to return to the top level and
select another configuration menu option. To take the
panel out of access level 3, press the
pushbutton.
Note:
The panel remains at access Level 2 until the cover
is relaced when access level is dependent on key
position.
Example 2
How do I set a delay of 1 min for sounder output circuit 2?
With the panel at access level 3, press the following
pushbuttons in the order shown:
Selects Sounder Outputs option
Use to select sounder circuit 2
Use to select delay to output - LED 10 illuminates
to confirm selection of sounder circuit delay.
To enable the configured output delay for sounder circuit
2, and with the panel at access Level 2, the
pushbutton must be pressed and the DELAY ON and
DISABLEMENT LEDs illuminate to confirm the panel has
a delay to outputs configured.
Press the
pushbutton to return to the top level and
select another configuration menu option. To take the
panel out of access level 3, press the
pushbutton.