997-532-000-1, Issue 1
March 2006
33
EN54 & ISO 7240 2-8 Zone Conventional Fire Panel - Installation & Configuration Manual
8
Specification
General
The Fire Control Panel is designed to comply with the
requirements of EN54 Part 2/4 and ISO 7240 Part 2/4. In
addition to the basic requirements of EN54-2 and ISO 7240,
the panel may be configured to conform with the following
optional functions - the applicable clauses of these standards
are referenced as follows:
Options
Clause
Controls:
Delay of the immediate actioning of outputs
7.11
Coincidence Detection
7.12
Test condition
10
Outputs:
Fire alarm device(s) (Sounders)
7.8
Fire alarm routing equipment
7.9
This panel complies with the European Low Voltage Directive
73/23/EEC (and the amending Directive 93/68/EEC), by the
application of the safety standard EN60950.
The panel conforms with the essential protection
requirements of the EMC Directive 89/336/EEC (and the
amending Directives 92/31/EEC and 93/68/EEC), by the
application of EN61000-6-3, (emissions) and EN50130-4,
(immunity).
Mechanical:
Construction:
Fire-resistant, ABS plastic moulded front
cover and back box. Cover contains all
user interface controls and visual
indicators.
Dimensions (mm): 318(h) x 356(w) x 96(d)
Approx. Weight:
2kg (no batteries)
Environmental:
Climatic classification: 3K5, (IEC 721-2-3)
Operating temperature: -5
o
C to +45
o
C, (recom5
o
C
to 35
o
C)
Humidity:
5% to 95% R.H.
Height above sea level:Maximum, 2000m
Panel sealing:
IP 30, (EN 60529)
Vibration:
EN 60068-2-6, 10-150Hz at 0.981ms
-2
,
0.1g
n
(Meets the requirements of
EN 54-2/4)
EMC:
Emissions:
EN 61000-6-3
Immunity:
EN 50130-4
Safety:
EN 60950
Summary of Contents for EN54