background image

External wiring

The external wiring should now be connected to the fire panel.

The fire panel is supplied with End Of Line Resistors for the zone and

sounder circuits, these must be transferred to the last device in the circuit.

The End Of Line Resistor must be replaced with Active End Of Line

device if removable smoke/heat detectors are used on the zone cirucit..

Please note these units are polarised.

1

DISCONNECT MAINS SUPPLY & BATTERY.

2

Connect the zone wiring, one zone at a time, transferring either the

End Of Line Resistor or Active End Of Line Device, if removable

smoke/heat detectors are being employed. The active end-of-line

devices are polarised and should be connected with Red/Orange

wire to the +ve and Black to the –ve.

3

Repeat the above procedure until all the required circuits are

connected.

4

Connect the sounder wiring one circuit at a time, transferring the end

of line resistor to the last sounder on that circuit.

5

Repeat the above procedure until all the required sounder circuits are

connected.

6

Connect other external circuits as required

7

Reinstate the mains supply, enter access code then press the

‘RESET’ button.

8

Refit plastic fascia. Do not over tighten two retaining screws.

61640610 issue 6_8/02

3

1 & 2 zone - Fire alarm panels

-

+

END-OF-LINE

RESISTOR 8K2 Ohms

fitted to last sounder

- +

2

FIRE PANEL

SOUNDERS

- +

1

+

-

-

+ +

-

-

+ +

-

Polarised and suppressed

sounders only

2nd

SOUNDER

COMMON

1st

SOUNDER

-

-

-

-

+

+

END-OF-LINE RESISTOR

8K2 Ohms fitted to last sounder

Volume

Figure 6 Connecting the Sounder circuit

COMMON

470 Ohms

680 Ohms

CALL POINT

- +

1

DETECTOR

ZONE

FIRE PANEL

COMMON

470 Ohms

680 Ohms

CALL POINT

black

red or

orange

Active

end of line

Fit an active end of line if

detectors are also connected

to the zone circuit.

8K2

Ohms

Figure 5 Connecting the manual call points

Base of existing range of detectors

- +

1

DETECTOR

ZONE

FIRE PANEL

L2

L1

OUT

IN L1

DIODE

(SCHOTTKY)

L2

L1

OUT

IN L1

DIODE

(SCHOTTKY)

Black

Red or

Orange

Active

End of Line

-

+

Remote

LED

LED

module

Connecting LED to base

with LED Module fitted

3 2 7

4

5

DC +ve

DC -ve

+ve

-ve

+ -

2 7

2 7

4

4

5

5

Active end of line

device

black

red or

orange

- +

1

DETECTOR

ZONE

FIRE PANEL

Base for new range of detectors

Figure 4 Connecting the Fire Detector and remote LED to a zone

circuit

CLASS

CHANGE

- +

AUX

24V

FIRE PANEL

Non latching alarm

remotely set by

an external source

Figure 7 Connecting the Class change circuit

Summary of Contents for ZIRCONLC1

Page 1: ...gured as a fault relay as standard EN54 requirement however the relay can be configured as an auxiliary fire relay by moving a jumper link from the fault position to the fire position on the back of t...

Page 2: ...back box and the transformer secondary wires are routed towards the right hand side The PCB locating holes should engage on the metal mounting tabs 4 Reconnect the transformer secondary wires to the P...

Page 3: ...mains supply enter access code then press the RESET button 8 Refit plastic fascia Do not over tighten two retaining screws 61640610 issue 6_8 02 3 1 2 zone Fire alarm panels END OF LINE RESISTOR 8K2 O...

Page 4: ...and then automatically reset 1 Enter the access code to get into supervisor mode if not already entered 2 Hold down the ADVANCE push button for at least 2 seconds until you hear a double bleep 3 The...

Page 5: ...ress reset to exit supervisor mode Note Pressing reset whilst the sounders are disabled will not revert the panel to normal operation 61640610 issue 6_8 02 5 1 2 zone Fire alarm panels Sounder General...

Page 6: ..._________________________ Site address___________________________________________________________________________ ______________________________________________________________________________________...

Page 7: ...61640610 issue 6_8 02 7 1 2 zone Fire alarm panels Fire panel event record Date Weekly Qtly Event Action Required Completed Name...

Page 8: ...8 61640610 issue 6_8 02 1 2 zone Fire alarm panels Date Weekly Qtly Event Action Required Completed Name...

Reviews: