Operating instructions
Access to “SUPERVISOR MODE” for panel
operation
To operate this fire alarm control panel, it is necessary to gain access to
the “Supervisor Mode”, to do this enter the four digit security password
code, on the yellow push buttons. This security code should have been
given to the responsible person on system hand over.
After entering the correct code the “Supervisor Mode” LED will illuminate.
The panel will time out of “Supervisor Mode” if the ‘RESET’ button is
pressed or 20 seconds have elapsed since the last button was pressed.
The following functions can all be employed in the “Supervisor
Mode”.
SOUNDER ON/OFF
If the panel is in alarm the sounders will sound, the sounder circuits may
be silenced by pressing this button. If the sounders are silent by pressing
this button they will be activated.
RESET
This will cause all faults and fires conditions to be cancelled, if a fault still
exists then it will re-appear within 10 seconds of this reset.
MUTE PANEL
To silence the panel’s internal buzzer press ‘MUTE PANEL’ push button.
The panel will continue to beep at a reduced rate until the condition
causing the buzzer to sound is rectified or reset.
SELECT - LAMP TEST
Hold down ‘SELECT / LAMP TEST’ push button for a minimum of two
seconds. Release once the test is complete.
Test Zone
This feature allows one person to check the detectors and sounders
without having to return to the panel during the testing routine. When the
appropriate zone is in test mode and a detector is activated, the sounder
circuit/s will operate for a few seconds and then automatically reset.
1
Enter the access code to get into “supervisor mode” if not already
entered.
2
Hold down the ‘ADVANCE’ push button for at least
2 seconds until you hear a double bleep.
3
The “Test” LED will light and the Zone 1 Fault LED will flash at a fast
rate (faster than the fault warning flash rate) the flashing LED at this
stage indicates that the zone is not in test!
4
If you do not wish to test this zone then press ‘ADVANCE’ to move
on to the next zone.
5
To put the zone into “Test” press ‘SELECT / LAMPTEST’ (repeated
pressing of this button will toggle the zone in and out of test mode!).
6
After you have pressed the select button you will see that the zone is
now constantly lit, this indicates that the zone is now in test!
7
Once the site tests have been completed you may find that the
keypad access timer has elapsed and that you will have to repeat
points 1-4 to get to the appropriate zone in test.
8
To cancel the test mode and return a zone back to normal operation
simply press ‘SELECT / LAMP TEST’ to toggle the zone from
constant to flashing.
Once you have returned the zone/zones to normal operation you can then
press reset to exit supervisor mode.
Note: Pressing reset whilst a zone is in test will not revert the panel to
normal operation!
4
61640610 issue 6_8/02
1 & 2 zone - Fire alarm panels
1
2
ZONE
FI E
R
POWER ON
GENERAL FAULT
SYSTEM FAULT
TEST
DISABLE
POWER FAULT
SOUNDER
FAULT/DISABLE
LED Continuous
DISABLED
LED flashing
FAULT
SUPERVISOR
MODE
5
SELECT /
LAMP TEST
4
ADVANCE
3
RESET
2
MUTE
PANEL
1
SOUNDERS
ON/OFF
FIRE
FAULT / DISABLED
To reset from alarm enter code
and press
SOUNDERS ON/OFF
followed by
RESET
Green indicator
Red indicators
Amber indicators
Amber indicators
Control buttons
Figure 8 Controls and indicators