EN: Installation Sheet 

Description  

The 2010-1-NB Network Board allows compatible fire and 
repeater control panels to be controlled in a peer-to-peer fire 
network. 

It provides redundancy in communications with two isolated 
RS-485 channels. Each channel is connected point-to-point to 
the network board in the next node in the fire network. It 
provides maximum signal integrity and communications quality 
at distances up to 1.2 km. 

If an open or short circuit occurs in the network wiring, the 
system indicates a fault (at the control panel) and continues to 
operate. 

Installation 

WARNING

: To avoid personal injury or death from 

electrocution, disconnect the control panel from the mains 
power supply and batteries before installing this product. 

To install the expansion board: 

1.  Unplug the power supply unit, the batteries, and any other 

device cables connected to the control panel PCB. 

2.  Remove the holding screw and unclip and remove the 

control panel PCB, as shown in Figure 1 (for two- and 
four-zone control panels, unclip the PCB at each corner by 
pressing carefully on the holding studs). 

3.  Install the network board connector J1 onto the control 

panel PCB connectors (located on the back of the PCB). 
Use connector J3 for the two- and four-zone control panel 
(see Figure 2), and connector J4 for the eight-zone control 
panel and the evacuation panel (see Figure 3). Push firmly 
to ensure a good connection. 

4.  Reinstall the PCB back into the control panel. 

5.  Connect data cables as shown in Figure 4. A connects to 

A and B connects to B (channel 2 connects to channel 1). 
Channels are marked on the rear of the network board. 

6.  Restore power and add the device to the control panel 

configuration (see the control panel installation manual for 
further details). 

Network configuration 

The network board allows for ring or bus configurations. 

Ring configuration 

This network configuration is recommended as it provides for 
redundancy in the transmission path. 

For ring configuration (class A), use both channels to connect 
all network nodes. 

Bus configuration 

Caution: 

Use this network configuration only in cases where 

the detection zones and mandatory EN 54-2 output functions 
are not remote between panels. 

This network configuration is not recommended. It does not 
provide for redundancy in the transmission path and creates a 
fire network with high fault sensitivity. 

Maintenance 

Basic maintenance consists of a yearly inspection. Do not 
modify internal wiring or circuitry. 

Specifications 

 

Typical current consumption 

50 mA at 24 VDC [1] 

Physical protocol 

RS-485 Isolated (between channels 
and control panel)  

Recommended cable 

Unshielded twisted pair wire or CAT 5 
0.129 to 3.31 mm

2

 (12 to 26 AWG) 

120 Ω ±10% characteristic impedance 
recommended 

Maximum distance between 
nodes 

1.2 km 

Temperature 
 

Operation 

 

Storage 

 

Relative humidity 

 
−5 to +40°C 

−20 to +50°C 
10 to 95% noncondensing 

Weight 

40 g 

Dimensions (W x H ) 

95 × 52 mm 

[1] Supplied by the control panel.

 

Regulatory information 

 

Certification 

 

Manufacturer 

UTC CCS Manufacturing Polska Sp. Z o.o. 