background image

© 2013 UTC Fire & Security. All rights reserved. 

1 / 2 

P/N 501-1761ZE-1-05 (EN) 

• REV 

05 

• ISS 

07JUN13 

 

A50E-

2 Line Relay Unit Installation Sheet

 

 

Description 

The A50E-

2 Line Relay Unit is an addressable device used to 

provide one Form C change over dry relay contact to control 

external appliances (door closers, fans, dampers, etc.) or 

equipment shutdown. The system firmware ensures that the 

relay is in the proper ON/OFF state. Upon command from the 

control panel, the relay energizes. TB2

-

6 and TB2

-

7 provide a 

normally

-

closed relay connection; TB2

-

7 and TB2

-

8 provide a 

normally

-

open relay connection. One device address is 

required. 

Up to 127 devices can be assigned to the loop. All devices 

incorporate a binary DIP switch enabling them to be given a 

unique address.

 

A red LED indicator illuminates when the unit 

has activat

ed. 

Installation 

Notes  

 

This module complies

 

with the requirements of 

EN 54-18. 

If the module is used in conditions or circumstances that 

do not comply with those tested for and allowed in 

EN 54-18

, operation may be impaired, and the supplier will 

not be liable for any injury suffered or damage caused as 

a result. You must contact our technical support 

department

 

for advice if the device is to be used in 

conditions

 

that

 

differ from those prescribed in EN

 54-18. 

 

This module will 

not 

operate without electrical power. As 

fires frequently cause power interruption, we suggest you 

discuss further safeguards with your local fire protection 

specialist

 

WARNING: 

Electrocution hazard. Dangerous voltages may be 

present at terminals even when the power is shut off

Take 

proper precautions to avoid injury or death.

 

Note: 

The A50E-

2 Line Relay Unit is shipped from the factory 

as an assembled unit; it contains no user

-

serviceable parts and 

should 

not 

be disassembled

 

To install the device: 

1. 

Verify that all field wiring is free of opens, shorts, and 

ground faults.

 

2. 

Make all wiring connections as shown in 

Figure 1. 

Notes:  

 

If a 2 in. (51 mm) 1

-

gang box is used, conduit can enter 

the electrical box through only one knockout hole.

 

 

If a 2

-1/

2 in. (64 mm) 1

-

gang box is used, conduit can 

enter the electrical box through one or both 

knockout

 

holes

Mounting 

The A50E-

2 can be mounted using any of three methods:

 

 

A DIN rail method for mounting multiple/single units

 

 

Adaptor plates for accessory box mounting

 

 

Single box mounting 

 

The u

nit can be mounted in a European 100mm square box. 

The terminal blocks will accept 14, 16, or 18 AWG wire (0.75, 

1.0, 1.5, mm²). Sizes 16 and 18 AWG are preferred.

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Reviews: