ZP2-A Series Operation Manual
Additional fire alarm status indications are:
• The control panel Alarm LED flashes if the alarm is activated by a detector or
is steady if it is activated by a manual call point.
• If a zone board is installed and the corresponding zone is included on the
zone board, then the zone alarm LED is flashing or steady (depending on the
source of the alarm).
• If a sounder delay has been enabled the Sounder Delay LED is steady.
• The Sounder Delay LED flashes while the delay is counting.
• The Sounder Start/Stop LED indicates the Sounder Start/Stop button status
(disabled, not disabled) and the status of the sounders (see Table 5 on page
6 for more information).
• If a fire routing delay has been enabled the Fire Routing Delay LED is steady.
The Fire Routing Delay LED flashes while the delay is counting.
• When fire routing is activated, the Fire Routing ON/Acknowledged LED
flashes. If configured to do so by your installation or maintenance contractor,
a steady Fire Routing ON/Acknowledged LED indicates that the fire routing
signal has been acknowledged by the remote monitoring equipment.
• If a fire protection delay has been enabled the Fire Protection Delay LED is
steady. The Fire Protection Delay LED flashes while the delay is counting.
• When fire protection is activated, the Fire Protection ON/Acknowledged LED
flashes. If configured to do so by your installation or maintenance contractor,
a steady Fire Protection ON/Acknowledged LED indicates that the fire
protection signal has been acknowledged by the remote monitoring
equipment.
• Alarm information for the first and last zones to report an alarm is displayed
on the LCD.
• The control panel buzzer sounds continuously.
Alarms activated by a manual call point always take priority over alarms activated
by a detector. When an alarm is activated by both devices, the Alarm LED is
steady.