Chapter 3: Configuration and commissioning
102
ZP2 Series Installation Manual
Sounders silence disable time
Note:
This feature is not available for control panels operating in NBN S21-100
or EN 54 Evacuation mode (any configured sounder silence disable times are
ignored).
To prevent the immediate silencing of sounders when an alarm is first reported,
the Sounder Start/Stop button may be temporarily disabled for a preconfigured
period of time when a configured sounder delay is counting down. The default
disable time for the Sounders Start/Stop button is 60 seconds.
The disable time starts to count down when the control panel enters alarm status
and the configured sounder delay starts.
During the configured disable time the Sounder Start/Stop LED is off and the
sounders cannot be silenced (before activation) by pressing the Sounder
Start/Stop button.
In the time between the end of the configured disable time and the end of the
configured sounder delay (when the Sounder Start/Stop LED is flashing),
pressing the Sounder Start/Stop button silences sounders (before activation).
A configured sounder delay may still be cancelled while the delay is running (and
sounders activated) by pressing the Sounder Delay button.
Loop Class configuration
Select Loop Class to configure the installation loop Class (Class A or Class B).
The default setting is Class A.
To configure a loop as Class A or Class B:
1. Select Field setup in Main menu.
2. Select Loop Class and select the loop number (1 for one-loop panel; 1 or 2 for
two-loop panel, etc.).
3. Select Class A or Class B.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......