Communication port specifications
Ethernet
Ethernet 10/100BaseT port (10 Mbps)
Note:
For increased security, we recommend against using
Ethernet for remote connection to the control panel via the
Internet.
TCP/IP
IPv4
USB host port
USB 2.0, type A connector
USB device port
USB 2.0, type B connector
Fire network specifications
Maximum distance between
two control panels
1.2 km
Maximum default capacity
32 loops and 32 nodes
Communication protocol
Proprietary protocol based on RS-485
Input and output specifications
Input and output overview
Configurable
outputs
General fire
outputs
General fault
outputs
24V AUX
output
Configurable
inputs
One-loop panel
2 Class B
1 Class A
2 (see note) 2 (see note) 1
2
Two-loop panel
4 Class B
2 Class A
2 (see note) 2 (see note) 1
2
Two-loop panel with
loop board
8 Class B
4 Class A
2
2
1
2
Repeater panel
0
2
2
1
2
Note: 1 supervised output and 1 potential-free relay.
Configurable inputs [1]
Number of inputs
2 supervised inputs, end-of-
line resistor 15 kΩ, 1/4 W
Active value
60.2 Ω
≤
active value
≤
8 kΩ (0.33 to 15 VDC)
Standby value
10 kΩ
≤
value
≤
20.2
kΩ (16.1 to 18.9 VDC)
Short circuit values
≤
60.2 Ω (less than 0.33 VDC)
High-impedance fault value
8 kΩ < value < 10 kΩ (15 to 16.1 VDC)
Open circuit values
≥
20.2 kΩ (>
18.9 VDC)
Configurable options
See Table 48 on page 86
[1] All values based on 2.5 A max. at 24 VDC (Imax. a, system voltage).
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......