Chapter 1: Introduction
ZP2 Series Installation Manual
7
Control/LED
LED colour
Description
Fire Routing Delay
button and LED
Yellow
Enables or disables a previously configured fire routing
delay. Cancels a delay as it counts down and activates
fire routing.
A steady LED indicates that a delay is configured and
enabled. A flashing LED indicates that a delay is
counting (fire routing is activated when the configured
delay elapses or when the delay is cancelled).
The countdown for an active (counting) fire routing
delay or extended fire routing delay is also displayed on
the product LCD (see Figure 3 on page 10):
•
When a fire routing delay is counting (and has not
been extended), the LCD displays FR in T1: xxx
sec.
•
When an extended fire routing delay is counting
(investigation time), the LCD displays FR in T2: xxx
sec.
Fire Routing
Fault/Disabled/Test
LED
Yellow
Indicates a fire routing fault, disablement, or test.
A flashing LED indicates a fault. A steady LED indicates
a disablement or a test.
Fire Protection
On/Acknowledged
button and LED
Red
Cancels a previously configured delay as it counts
down and activates fire protection.
A flashing LED indicates that fire protection has been
activated. A steady LED indicates that the fire
protection signal has been acknowledged by the remote
monitoring equipment.
Fire Protection Delay
button and LED
Yellow
Enables or disables a previously configured fire
protection delay. Cancels a delay as it counts down and
activates fire protection.
A steady LED indicates that a delay is configured and
enabled. A flashing LED indicates that a delay is
counting (fire protection is activated when the
configured delay elapses or when the delay is
cancelled).
Fire Protection
Fault/Disabled/Test
LED
Yellow
Indicates a fire protection fault, disablement, or test.
A flashing LED indicates a fault. A steady LED indicates
a disablement or a test.
Sounder Delay button
and LED
Yellow
Enables or disables a previously configured sounder
delay. Cancels a delay as it counts down and activates
sounders.
A steady LED indicates that a sounder delay is
configured and enabled. A flashing LED indicates a
delay is counting (sounders are activated when the
configured delay elapses or when the delay is
cancelled).
Sounder
Fault/Disabled/Test
LED
Yellow
Indicates a sounder fault, disablement, or test.
A flashing LED indicates a fault. A steady LED indicates
a disablement or a test.
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......