Chapter 3: Configuration and commissioning
46
ZP2 Series Installation Manual
5. Press F2 (Exit) to exit the menu.
Repeat to enable a disabled feature or device.
Notes
•
Active outputs cannot be disabled.
•
Devices or zones in alarm are not disabled until the control panel is manually
reset.
•
In maintenance level operation, to disable Class A outputs each output used
must be disabled (for example, if OUT1 and OUT2 are combined to create a
single Class A output, then both OUT1 and OUT2 must be disabled
individually).
The Test menu
Use the Test menu to test system features or devices. The following features or
devices can be tested from this menu:
•
Zones
•
Control panel input activation
•
Control panel and loop output activation
•
Output group activation
•
Device LED activation
•
Remote features and devices
•
Batteries
Note:
Tests for outputs and output groups (local or remote) continue for as long
as the test screen is visible. There is no automatic timeout for the output
activation test and system information will not be visible on the LCD for the
duration of the test. Operation not related to the activation test continues as
normal in the background.
Testing zones
To test a zone:
1. Select Test from the Main menu.
2. Select Zones.
3. Select the zone to test, and then press the jog dial to start the test. Press the
jog dial again to end the test for the selected zone.
By default you can select and test up to a maximum of four zones to test at
the same time (the maximum number of zones in test is configurable - see
“Zone configuration” on page 79).
4. Press F2 (Exit) to exit the menu.
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......