Chapter 3: Configuration and commissioning
50
ZP2 Series Installation Manual
Report
Description
Zone status [1]
Displays the current status information for zones.
Zone mapping [1]
Displays which devices are assigned to each zone in your fire system.
Device status [1]
Displays the current status information for control panel devices.
Device information available in real time includes: instant, mean,
maximum, and minimum analog values, alarm level, communication
error rate, and the loop input contamination level.
Panel I/O status
Displays the current status information for the control panel inputs and
outputs.
Output Groups status [1] Displays the control panel output groups (sounders, fire routing, fire
protection, or program) that are currently active.
Rules status
Displays the control panel rules that are currently active. A rule
consists of one or more states (combined by Boolean operators) that
are configured to trigger specific system actions after a specific
confirmation time. Rules are created using the configuration utility.
Firenet status
Displays the current status for all control panels in the fire network.
Save/Print reports
Saves or prints reports.
PAK List
Displays details of all PAKs currently registered to the control panel.
[1] These reports are not available for repeater panels.
Viewing or clearing the event log
Select View all or Clear to view or clear alarm, fault, and condition events logged
by the control panel.
To view or clear the event log:
1. Select Reports from the Main menu.
2. Select Event log, and then select View all (to view all current entries) or Clear
(to delete all current entries).
3. Press F2 (Exit) to exit the menu.
The event log can include a maximum of 9,999 entries. When the maximum
number of entries is reached, the oldest entries are deleted as new entries are
recorded.
Backing up the event log
Select Backup to create a backup of the event log. The backup reports are saved
to a USB flash drive (not supplied) in XML format and can be viewed with the
Configuration Utility.
To back up the event log:
1. Open the control panel cabinet door.
2. Insert a USB flash drive into either of the USB connectors (Figure 21, item 1).
3. Close the control panel cabinet door.
Summary of Contents for ZP2 Series
Page 1: ...ZP2 Series Installation Manual P N 00 3251 501 0003 04 ISS 04MAY15...
Page 6: ...iv ZP2 Series Installation Manual...
Page 20: ...Chapter 1 Introduction 14 ZP2 Series Installation Manual...
Page 114: ...Chapter 3 Configuration and commissioning 108 ZP2 Series Installation Manual...
Page 128: ...Chapter 5 Technical specifications 122 ZP2 Series Installation Manual...
Page 142: ...Appendix C Menu maps 136 ZP2 Series Installation Manual...
Page 148: ......