P/N 501-1244ZE-1-05 • REV 05 • ISS 05MAR14 

After installation, ensure that the detector communicates with 
the control panel. Always test detectors after installation. 

To remove a locked detector: 

1.  Insert a small screwdriver into the locking tab slot  

(Figure 3). 

2.  Press and rotate the detector anticlockwise. 

Setting the address 

The detectors include a seven-segment DIP switch (SW1) for 
assigning device addresses. Each switch segment has a 
decimal value as shown in Figure 4. The address is the sum of 
all the switch segments in the ON position. The full DIP switch 
address range of 1 to 127 is shown on page 4. 

For example, to select a device address of 007, set SW1-1, 
SW1-2, and SW1-3 to the ON position and the remaining 
switch segments to the OFF position. 

Locking base option 

The sensors are compatible with a range of bases (see 
“Specifications”) and are easily installed by a simple twist and 
lock action.  

Note: 

To prevent unauthorised removal of a device from its 

base, an automatic locking tab is incorporated into all sensor 
mouldings. If the tab is removed, sensors can only be released 
from their bases by use of a screwdriver, as shown in Figure 3. 
This locking option is applied at the system commissioning 
stage. 

Maintenance and testing 

Basic maintenance consists of a yearly inspection. Do not 
modify internal wiring or circuitry. 

Automatic self-test 

Sensor sensitivity, calibration and self-testing are carried out 
automatically by the fire panel. Removal or replacement of an 
incorrect sensing device will be identified by the system and 
shown as a fault. 

 

Specifications 

 

 

ZP730-2P/2B 
ZP730-2S30 

ZP720-3P 
ZP732-2P 
ZP732-2S30 

Operating voltage 

19.5 to 20.5 VDC 

19.5 to 20.5 VDC 

Current 
 

Standby 

 

Alarm 

 
600 µA 
700 µA 

 
600 µA 
700 µA 

Coverage 

ZP730-2P/2B: 100 m

ZP730-2S30: 100 m

 

ZP720-3P: 50 m

ZP732-2P: 100 m

smoke element/ 
50 m

thermal element  

ZP732-2S30: 100 m

smoke element/ 
50 m

thermal element 

IP Rating 

IP32 

IP32 

Polarity sensitive 

Yes 

Yes 

Compatible bases 

ZP7-IB-P  
ZP7-SB1-B  
ZP7-SB1-P  
ZP7-RB1-P 
ZP755B-2P 
ZP755BV-3 
ZP755BV-4P 
ZP755BV-5P 

ZP7-IB-P  
ZP7-SB1-B  
ZP7-SB1-P  
ZP7-RB1-P 
ZP755B-2P 
ZP755BV-3 
ZP755BV-4P 
ZP755BV-5P 

Compatible 
accessories 

Z-RL4 Remote LED 
unit 

Z-RL4 Remote LED 
unit 

 

Operating 

 

temperature 

 

Storage 

 

temperature

 

Relative 

 

humidity 

–10 to +75°C 
 
–20 to +70°C 
 
20 to 95% 
noncondensing 

–10 to +85°C 
 
–20 to +70°C 
 
20 to 95% 
noncondensing 

Dimensions (Ø x H) 

106 × 52 mm 

ZP720-3P

:  

106 × 52 mm

  

ZP732-2P: 

106 × 58 mm

 

ZP732-2S30:

  

106 × 58 mm 

Weight 

105 g 

ZP720-3P: 85 g 
ZP732-2P: 105 g 
ZP732-2S30: 105 g 

Regulatory information 

This section includes both regulatory information and a 
summary on the declared performance according to the 
Construction Products Regulation 305/2011. For detailed 
information refer to the product Declaration of Performance. 

 

Certification 

 

Certification body 

0370 

Declaration of 
Performance number 
 

ZP720-3P 

 

ZP730-2P/2B/2S30 

 

ZP732-2P/2S30 

 
 
360-4211-0399 
360-4211-0199 
360-4211-0299 

Year of first CE marking 

05 

Product Identification 

ZP720-3P 
ZP730-2P 
ZP730-2B 
ZP730-2S30 
ZP732-2P 
ZP732-2S30

 