background image

© 2021 Carrier. All rights reserved. 

1 / 4 

P/N 10-5202-501-ZV01-12 • ISS 05OCT21 

 

ZP755BV-4P Addressable Base Sounder with 

Visual Indicator Installation Sheet 

 

Description 

The ZP755BV-4P is an addressable base sounder with visual 

indicator, designed for use in Ziton addressable fire detection 

and alarm systems.  

Note: 

The visual indicator of this product does not comply with 

EN 54-23 and must not be used in fire alarm installations 

where fire notification beacons are required. 
The sounder includes a volume control, an address-setting 

switch, programmable tone settings, and a pair of jumpers to 

select the operating power — from the addressable loop or an 

external supply. The device plugs into a base that is purchased 

separately. See Table 1 for a list of model numbers. 

Table 1: Models 
Model 

Description 

ZP755BV-4P 

Base sounder/Visual indicator, Polar white 

ZP755-COV-P 

Cover for ZP755B Base sounder  

with no detector, Polar white 

ZP755-COV-R 

Cover for ZP755B Base sounder  

with no detector, Red 

SPB–2P 

Mounting base, Polar white 

Installation 

To install the device: 

1.  Wire the base 
2.  Set the operating power 
3.  Set the address 
4.  Set the operating mode 
5.  Set the tone 

6.  Set the volume 
7.  Mount the sounder onto the base 
The details of each step are given below 

Wiring the base 

Connect the loop wiring for the base as shown in Figure 1. 

There is no wiring between the sounder and base. 

Figure 1: Loop wiring for the base 

 

1.  Ext. 24 VDC+ IN/OUT 

4.  Ext. 24 VDC ground IN/OUT 

5.  Loop+ IN/OUT 

7.  Shield 

8. 

Loop − IN/OUT

 

Setting the operating power 

The sounder includes a pair of power selection jumpers, J1 

and J2. To select the source of the sounder operating power, 

position the jumpers as shown in Figure 2. 

Figure 2: Power-selection jumper configuration 

 

1.  Loop powered 

 

2.  External 24 VDC 

Note: 

When using an external power supply, use only one that 

is CE and EN 54-4 compliant to power all the sounders on the 

same loop. Ensure connection to number 1 and number 4 in 

addition to the loop wiring number 5 and number 8. 

8

4

5

1

J1

J1

J2

J2

2

1

Reviews: