background image

© 2014 UTC Fire & Security. All rights reserved. 

1 / 4 

P/N 501-1780ZE-1-10 • REV 10 • ISS 16APR14 

 

ZP755HAV-2 Addressable Horn Sounder/Visual 
Indicator Installation Sheet 

 

Description 

The ZP755HAV-2 is an addressable horn sounder/visual 
indicator designed for use in Ziton analogue addressable fire 
detection and alarm systems. 

Note: 

The visual indicator of this product does not comply with 

EN 54-23 and must not be used in fire alarm installations 
where fire notification beacons are required. 

The device includes a volume control, an address-setting 
switch, programmable tone settings, and a pair of jumpers to 
select the operating power — from the analogue addressable 
loop or an external supply. The device plugs into a base that is 
purchased separately. See Table 1 for a list of model numbers. 

Table 1: Models 

Number 

Description 

Sounder: 
 

ZP755HAV-2R

 

ZP755HAV-2P 

 
Horn sounder, red 
Horn sounder, polar white 

Base: 
 

SPB-2R 

 

SPB-2P 

 
Base, red 
Base, polar white 

Installation 

To install the device; 

1.  Wire the base 

2.  Set the operating power 

3.  Set the address 

4.  Set the mode of operation 

5.  Set the tone 

6.  Set the volume 

7.  Mount the sounder/visual indicator onto the base 

The details of each step are given below. 

Wiring the base 

Connect the loop wiring for the plug-in base as shown in 
Figure 1. There is no wiring between the sounder and base. 
The base is supplied separately. 

Figure 1: Loop wiring for the base 

 

1. 

Ext. 24 VDC+ IN/OUT  

2. 

Ext. 24 VDC ground IN/OUT 

5. 

Loop+ IN/OUT 

6. 

Loop − IN/OUT 

7. 

Shield 

 

Setting the operating power 

The sounder includes a pair of power selection jumpers, J1 
and J2. To select the source of the sounder operating power, 
position the jumpers as shown in Figure 2. 

Figure 2: Power selection jumper configuration 

 

1. 

Loop powered 

 

2. 

External 24 VDC 

Note: 

When using an external power supply, use only one that 

is CE and EN 54-4 compliant to power all the sounders on the 
same loop. 

6

2

5

1

J1

J1

J2

J2

2

1

Reviews: