background image

Ziton Wireless Manual Call Point Installation Guide

General

The Ziton wireless manual call point is available under 

the following part number:

PART NO   

VARIANT TYPE

ZR485-3   

Ziton wireless manual call point

The address of the unit is set when programming the 

device to the system (see programming manual for 

details). The installation must conform to BS5839:Part 1 

(or applicable local codes). 

Installation of Ziton wireless manual call point

Loosen the back plate fixing screw. Insert flat bladed 

instrument into the removal slot and remove the back 

plate from the transmitter/battery section. (See Figure 1).

Mount the back box 1.4m from the floor, using suitable 

fixings and fasteners. A minimum of two mounting holes 

must be used. Countersunk head screws must be used to 

avoid the possibility of damage to the internal 

components. (See Figure 2).

Figure 1

Power jumper

Figure 2

Figure 3

Wall mounting positions

To ensure correct operation, connect the power jumper 

across the PIN header on the battery PCB located on the 

rear of the call point as shown in Figure 3. 

Specification

Operating 
Temperature

 

-10 to +70°C (ambient)

Storage 
Temperature

 

0 to +35°C

Humidity

  

Up to 95% non-condensing

Supply

   

6x AA Alkaline (Panasonic LR6AD  

 

 

Powerline / Varta 4006 Industrial) 

IP Rating 

 IP24

Operating 
Frequencies

 

868 MHz

Output Transmitter
Power

 

 

Variable 0-14 dBm

Dimensions

 

89mm (W) 92mm (H) 70mm (D)

Weight 

 0.40kg

Regulatory information

Manufacturer

 

EMS Ltd.    

 

 

 

 

Technology House, Sea Street,    

 

 

Herne Bay, Kent, CT6 8JZ, 

  United 

Kingdom

Year of
manufacture

 

See serial number on unit

Certification

Certification body

 

CPD Certificate
DOP

  

0359-CPR-0168

Approved to

 

EN54-11

  EN54-25

Application

 

Intended for use in fire detection

 

 

and fire alarm systems in and

 

 

around buildings. Indoor use only.

European Union

directives 

 

EMS declares that the radio  

 

  equipment 

type 

Ziton Wireless    

 

 

Manual Call Point is in compliance  

 

 

with Directive 2014/53/EU. The full  

 

 

text of the EU declaration of  

 

 

 

conformity is available at the  

 

 

 

following internet address:  

 

 

                 

      

www.utcfssecurityproducts.eu/dop/ 

 

 

 

2012/19/EU (WEEE directive):

 

 

Products marked with this symbol  

 

 

cannot be disposed of as unsorted  

 

 

municipal waste in the  European  

 

 

Union. For proper recycling, return  

 

 

this product to your local supplier  

 

 

upon purchase of equivalent new  

 

 

equipment, or dispose of it at

 

 

designated collection points. 

 

 

For more information see

  www.recyclethis.info

 

 

Dispose of your batteries in an    

 

 

environmentally friendly manner  

 

 

according to your local regulations.

Contact information

For contact information, see www.utcfireandsecurity.com
 