5.1
DIP Switch Settings
Fig. 5.2
1.
In DIP Switch 1, ON is for NC (Normally Closed) and OFF for NO (Normally Open). (Default mode,
do not modify)
2.
In DIP Switch 2, ON is for automatic opening and OFF is for self-locking when the power is off.
3.
In DIP Switch 3, ON is for automatic stop and OFF is for automatic reversing when the boom
meets an external obstacle.
4.
With DIP Switch 4, auto-closing speed can be adjusted. ON is for auto-closing speed of 1.3s
whereas OFF is for 0.9s for the boom. (for the ProBG3030 model only)
5.
The DIP Switch 5, 6, 7, 8 are used for delaying automatic closing of the boom. The delay time for
automatic closing of the boom can be set are 1s, 2s, 3s, 4s, 5s, 8s, 10s, 15s, 20s, 25s, 30s, 35s, 40s,
50s, 60s as shown in Fig. 5.2.
6.
If the boom cannot reach the vertical position due to any obstacle, the boom can be adjusted at
an angle of 60°, 70°, 80°, and 90°. A separate DIP switch is provided on the board for the same (1,
2 Switches).
7.
The maintenance mode switch is convenient for possible repairing and adjusting.
(Default mode,
do not modify).