SBT2000S Swing Barrier Turnstile

 

 

 

 

 

 

  

 

User Manual 

P a g e

 | 13 

 

 Copyright©2020 ZKTECO CO., LTD.  All rights reserved. 

When setting the zero position, you can manually push the swing arm for fine-tuning. If the swing 
arm exceeds a certain angle, it will be invalid. (At this time, the digital LED displays 02E000). 

3.

 

Passing Mode(03EXXX) 

 

(03E000) Right control, left control (default) 

 

(03E001) Right control, left forbidden 

 

(03E002) Right forbidden, left control 

 

(03E003) Right forbidden, left forbidden 

Examples are as follows:

 If you want to set the gate access mode as Right controlled, Left forbidden. 

Step 1: 

Long press "MENU" to enter Settings. Short press the MODE button twice to enter the access 

mode (03EXXX). 

Step 2:

 Press "ADD" or "DEC" to adjust the function parameters value (03E001). 

Step 3:

 Long press the "MENU" button to save the parameters after adjustment. 

4.

 

Automatic Closing Time for Unmanned Passage(04EXXX) 

After pedestrian passes through the last infrared sensor, the gates will remain open for the specified 
time, then closes immediately. The valid value for Automatic Closing Time can be set between 1 to 60 
seconds and the default value is 5s. 

5.

 

Gate Opening Speed(05EXXX) 

Set the Gate Opening Speed to open the gate. The smaller the number is set, the faster the speed. The 
Gate Opening Speed value can be set between 1 to 5 and the default value is 3. 

6.

 

Gate Opening Deceleration Distance(06EXXX) 

The larger the number, the longer the deceleration time and the more stable the swing arm operation. 
The Gate Opening Deceleration Distance can be set between 10 to 25 and the default value is 16. 

7.

 

Gate Closing Speed(07EXXX) 

Set the Gate Closing Speed to close the gate. The smaller the number is set, the faster the speed. The 
Gate Closing Speed value can be set between 1 to 5 and the default value is 3. 

8.

 

Left Gate Closing Deceleration Distance(08EXXX) 

The larger the number, the longer the deceleration time and the more stable the swing arm operation. 
The Left Gate Closing Deceleration Distance value can be set between 10 to 25 and the default value 
is 16. 

 

 

Summary of Contents for SBT2000S

Page 1: ...the instructions carefully before operation Follow these instructions to ensure that the product is functioning properly The images shown in this manual are for illustrative purposes only For further...

Page 2: ...liar with the design and that the said personnel have received thorough training in operating and maintaining the machine unit equipment It is further essential for the safe operation of the machine u...

Page 3: ...the machine unit equipment and such amendments shall not give any right to claim any compensation or damages under any circumstances ZKTeco shall in no way be responsible i in case the machine unit eq...

Page 4: ...t research and development of biometric verification procedures and the productization of biometric verification SDK which was initially widely applied in PC security and identity authentication field...

Page 5: ...a table and field names are inside square brackets For example pop up the New User window Multi level menus are separated by forwarding slashes For example File Create Folder Symbols Convention Descri...

Page 6: ...ORKING PRINCIPLE 8 1 4 TECHNICAL SPECIFICATIONS 8 1 5 2 INSTALLATION 9 INSTALLATION NOTES 9 2 1 INSTALLATION POSITION 9 2 2 CABLES INSTALLATION AND FIXATION 9 2 3 3 MENU THEIR FUNCTIONS 12 FUNCTION IN...

Page 7: ...he secured side During emergencies the barriers automatically swing thereby ensuring users fast unencumbered exit to safety During power outage the user can push through the barrier easily to exit to...

Page 8: ...oller IR sensor and the Transformer Reader The reader reads the data in the RFID smart card and sends it to the controller Control panel The control panel is the system s control center that receives...

Page 9: ...t the card is being read successfully And then the reader sends signals to the access controller to request permission to pass through the passage If the signal is authorized the access controller wil...

Page 10: ...as well as at each movable part of the swing barrier turnstile Any loose nuts screws and other fasteners should be tightened in time to avoid any failures caused by long time operations Installation...

Page 11: ...tand and the edge of the chassis base on the ground according to the sizes as shown in the above figure Use a hammer drill to perforate M12 screw holes and then install the screws Place the swing barr...

Page 12: ...SBT2000S Swing Barrier Turnstile User Manual P a g e 11 Copyright 2020 ZKTECO CO LTD All rights reserved...

Page 13: ...g the upper menu item and increasing the value DEC It is used for navigating to the lower menu item and decreasing the value Menu Introduction 3 2 1 Display Mode 01EXXX 01E000 Display current position...

Page 14: ...e last infrared sensor the gates will remain open for the specified time then closes immediately The valid value for Automatic Closing Time can be set between 1 to 60 seconds and the default value is...

Page 15: ...value of Clutch Start Angle can be set between 1 10 The default value is 1 12 Clutch Unlock Mode 12EXXX The different Clutch Unlock Modes are as follows 12E000 Delayed unlock 12E001 Swipe to unlock d...

Page 16: ...l work default 18E001 Reset Error Code 3 3 Error Code Cause ER0002 Power on Self test failure Hall limit detection error ER0004 Run Timeout ER0008 Clutch Locked ER016 The code disk detection failed ER...

Page 17: ...SBT2000S Swing Barrier Turnstile User Manual P a g e 16 Copyright 2020 ZKTECO CO LTD All rights reserved Wiring Diagram and Function 3 4 Check circuit according to the following wiring diagram...

Page 18: ...C button These buttons control the barrier to open to the left or right side 4 Access control power supply It supplies power for the access board 5 RS485 communication port It is used for receiving ex...

Page 19: ...th movement Check and tighten other connection parts Power Supply Maintenance 4 3 Cut off power supply before maintenance Check whether any of the plug nut screw or fastener is loose if it is then it...

Page 20: ...oder wiring error Cause It may be due to reversed wiring of encoder A and B phase Solution Please check if the wiring of encoder A and B phase is reversed If yes replace it 5 The direction of gate ope...

Page 21: ...ZKTeco Industrial Park No 26 188 Industrial Road Tangxia Town Dongguan China Phone 86 769 82109991 Fax 86 755 89602394 www zkteco com Copyright 2020 ZKTECO CO LTD All Rights Reserved...

Reviews: