4. Cable Diagram 

4.1 Function description of the turnstile control board 

If you are using TS1011 or TS1022, all the connections between access control and turnstile control boards are done in 
factory. Just plug in communication cable to access controller and do the setting. 

If you are using TS1000, you need to connect access control system to the control board, please check the content in this 
chapter carefully. 

Warning: 

The third party access control system lock relay trigger time should be 1 second or less than 1 second. 

 

  Figure 4-1

 

Descriptions: 

J2 Counter: 

To connect a LED screen and display the number of people passed that is generated by the push of tripod arms, 

each completed push means pass one time.

 

J5 (Right) & J4 (Left) Indicator:

 To connect a LED screen and indicate whether this passage is allowed to pass.

 

J3 Indicator (top): 

To connect a LED screen and indicate if user verification is successful and whether it is able to pass. 

J-NC2 Disabled Turnstile: 

Short circuit NC1 and GND, the turnstile is disabled, that is to say, the turnstile is locked by force.

 

J7 Opening Signal Input:

 To receive relay signal and open the turnstile.

 S

hort circuit K1 and GND, left passing is allowed; 

short circuit K2 and GND, right passing is allowed. 

J6 External Alarm:

 Short circuit ALARM1 and GND, and the turnstile is disabled (locked) and the alarm is ringing in case 

there are emergencies. 

Summary of Contents for TS1000 Series

Page 1: ...TS1000 Series Vertical Tripod Turnstile User Manual Version 2 4 Date Jan 2018...

Page 2: ...Degree IP54 Operating Environment Indoor and Outdoor shelter Arm Length mm 520 Operating Temperature 28 C 60 C Net Weight 34kg Operating Humidity 5 85 Gross Weight 40kg Flow Rate 25 30 passages minut...

Page 3: ...1 Please make sure that the power requirements are strictly met to avoid permanent damage to the unit Input voltage AC 100 120V 200 240V Note The tripod turnstile must be connected to the ground eart...

Page 4: ...3 Setting a warning line for card swiping see Figure 3 2 A warning line is suggested to prompt users to swipe cards in a distance which would greatly reduce the probability of equipment failure cause...

Page 5: ...levelness of the mounting plate If the mounting plate is not level adjust it by the gaskets provided Note that all the four expansion bolts must be installed properly as shown in Figure 3 4 Figure 3...

Page 6: ...nd display the number of people passed that is generated by the push of tripod arms each completed push means pass one time J5 Right J4 Left Indicator To connect a LED screen and indicate whether this...

Page 7: ...t otherwise will damage the control board 4 3 DIP K1 switch configuration Figure 4 3 Pin 1 2 3 4 5 6 7 8 Function Setting Opening Duration Direction Indicator Continue Passing Function Alarm Default 1...

Page 8: ...Alarm function optional In the DIP K1 switch number 8 is used to enabled or disabled the Alarm Function 1 enabled 0 disabled Note Please set to 0 when working normally that is to say that Alarm Funct...

Page 9: ...ous positions for prompting passers by to pass in a proper way and in good order Reasonable maintenance consciousness helps to guarantee long term usage of the tripod turnstile Regular maintenance Cle...

Page 10: ...circuit the ports K1 GND and K2 GND if the turnstile is successfully opened it would be the problem of controller In this case please refer to Attachment 2 Connection Diagram of Control board and Acc...

Page 11: ...IP 192 168 1 201 5 Turnstile Opening Duration 5s 6 Passing Direction Indicator Passing is allowed in both directions 7 Continue Passing Function Disabled 8 Alarm Function Disabled Note The Lock Drivin...

Page 12: ...tion Diagram of Control board and Access Control Panel Warning This is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to t...

Reviews:

Related manuals for TS1000 Series