7
Frequenc
y Range
46Hz~54Hz
Power
Factor
0.99
0.95
Output
Voltage
220VAC×(1±1%)
Current
27A
45A
68A
91A
Frequenc
y
46Hz~54Hz (Line Mode. Same as input frequency), 50Hz×(1±0.1%)(Battery Mode)
Power
Factor
0.8
Overload
Capability
105%
~
125%,
1 minutes minimum, then transfer to bypass and alarm
,
Bypass over
load > 30 minutes then turn off output
;
125%
~
135%
,
30 seconds minimum, then transfer to bypass and alarm
.
Bypass over
load > 1 minutes then turn off output;
;
>135%
,
0.5 seconds minimum, then transfer to bypass and alarm.
Crest Factor 3
:
1
THD
THD<2% ( Linear Load)
Battery(
High ambient temperature shortens the battery’s lifetimes
)
Backup Time 4minutes
(Full Load)
Depend on
the capacity
of external
battery
3minutes
(Full Load)
Depend on the capacity of external battery
Recover
Time
<7 Hours
Comeback
to 90%
Depend on
the capacity
of external
battery
<7 Hours
Comeback
to 90%
Depend on the capacity of external battery
*.
The maximum input current is got at input 187V, full load and full
charge current.
Model
EX6K
EX6KL
EX10K EX10KL EX3110KL EX3115KL EX3120KL
EMC
ESD
IEC61000-4-2 Level 4
RS
IEC61000-4-3 Level 3
EFT
IEC61000-4-4 Level 4
Surge
IEC61000-4-5 Level 4
Operating
Temperature
0
℃~
40
℃
Summary of Contents for EX series
Page 1: ...EX SERIES EX6K L EX10K L EX3110K L EX3115K L EX3120K L USER MANUAL...
Page 8: ...4 1 2 Front View 1 3 Rear View EX6KL EX10KL EX6K EX10K EX3110KL EX3115KL EX3120KL EX10K EX6K...
Page 9: ...5 EX6KL EX10KL EX3110KL EX3115KL EX3120KL...
Page 20: ...16...
Page 21: ...17...
Page 25: ...21...
Page 33: ...29 4 2 Operate mode 1 AC mode AC Mode 2 Battery Mode Battery Mode...
Page 34: ...30 3 Standby Mode Standby Mode 4 Bypass Mode Bypass Mode...